Samlexpower Evolution EVO-2212 Owner's Manual - page 120
28 | SAMLEX AMERICA INC.
APPENDIX A
SECTION 4 |
Parameter Setup
1 = Normal/Fault. When the EVO Inverter Charger is in Fault Mode, the status Relay turns
ON. The Relay is OFF when not in Fault Mode.
2 = Generator. When the battery voltage is lower than “LOW VOLT ALARM”, the Status
Relay turns ON. When the battery voltage is higher than the “RESET VOLTAGE”, the
Status Relay turns OFF. This function may be used for Generator Auto Start/Stop in
conjunction with optional external Generator Auto Stop/Start Module.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
OTHER FUNCTION
RELAY FUNCTION
2 = Generator
POWER SAVING
1 = Enable
Up Key x 4
ò
Enter Key
ò
Up Key x 4
ò
COMM ID:
Communication ID- This sets the ID number for the COMM Port and EVO-RC Remote Control.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
OTHER FUNCTION
COMM. ID
1
POWER SAVING
1 = Enable
Up Key x 4
ò
Enter Key
ò
Up Key x 5
ò
BUZZER:
Set the buzzer ON/OFF.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
OTHER FUNCTION
BUZZER
1 = ON
POWER SAVING
1 = Enable
Up Key x 4
ò
Enter Key
ò
Up Key x 6
ò
DISCHARGE BEEP:
To select the buzzer ON/OFF while in "Inverting Mode".
SELECT GROUP
CHARGE CURVE
SELECT GROUP
OTHER FUNCTION
DISCHARGE BEEP
0 = OFF
POWER SAVING
1 = Enable
Up Key x 4
ò
Enter Key
ò
Up Key x 7
ò
DEFAULT RESET
This is to reset all of the parameters to the Default Values.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
OTHER FUNCTION
DEFAULT RESET
0 = No
POWER SAVING
1 = Enable
Up Key x 4
ò
Enter Key
ò
Up Key x 8
ò
DATALOG TIME AND DATALOG DISABLE:
Set the time period of the data log.
0 = Disable
1 = 1 sec
2 = 10 sec
3 = 30 sec
4 = 60 sec
5 = 5 min
6 = 10 min
SELECT GROUP
CHARGE CURVE
SELECT GROUP
OTHER FUNCTION
DATALOG TIME
1 = 1 sec
POWER SAVING
1 = Enable
Up Key x 4
ò
Enter Key
ò
Up Key x 9
ò
PARAMETER SAVE
Save all parameters to SD Card. (see Details at Section 5)