Samlexpower Evolution EVO-2212 Owner's Manual - page 48
48 | SAMLEX AMERICA INC.
Electrical Code) - Section 210.19(A)(1)(a) regarding minimum Ampacity and size of
Branch Circuit Conductors.
6) Column 7 indicates the wiring conductor size that has been determined based on
NEC-2014 (National Electrical Code) - Ampacity Table 310.15(B)(16) for Raceway.
This conductor size is based on (i) NEC Ampacity (Column 6) (ii) conductor temper-
ature of 75°C and (iii) ambient temperature of 30°C / 86°F.
7) Column 8 indicates the Amp rating of EXTERNAL breaker that is required to be
installed in the Load Center / Breaker Panel feeding the unit. The Amp rating of
this breaker is based on the following considerations:
a. Not less than the NEC Ampacity (Column 6) - Refer to NEC-2014 (National
Electrical Code) - Section 210.20(A) regarding overcurrent protection of
Branch Circuit Conductors
b. Closest Standard Ampere Rating of Breaker has been used - Refer to NEC-
2014 (National Electrical Code) - Section 240.6(A) regarding overcurrent
protection
c. Where Standard Breaker Rating does not match the required NEC Ampacity
(Column 6), the next higher Standard Rating of the breaker has been used -
Refer to NEC-2014 (National Electrical Code) - Section 240.4(B) regarding over
current devices
d. Type of breaker: Standard circuit breaker for 120VAC Load Center /Breaker
Panel
3.9 SIZING OF WIRING AND BREAKERS - AC OUTPUT SIDE
WARNING!
AC Breakers for the AC output circuits have NOT been provided internally. These have to be
provided externally by the installer / user based on guidelines given below. Please note that
guidelines given below on wire sizing and over-current protection will be superseded by the
applicable National / Local Electrical Codes
ATTENTION!
Breakers AC pour les circuits d’entrée AC ont pas été fournis en interne. Ceux-ci doivent être fournies à l’extérieur par
l’installateur / utilisateur sur la base des directives données ci-dessous. Se il vous plaît noter que les directives ci-dessous
sur dimensionnement des câbles et protection contre les surintensités seront remplacées par les nationaux / codes
électriques locaux applicables.
3.9.1 Tables for Wire and Breaker Sizing - AC Output Side
Table 3.3 provides details of wire and breaker sizing for the AC output side.
AC wiring and breaker sizes on the AC output side are required to be determined by the
Rated Load Current when operating in Inverter Mode (Column 1).
SECTION 3 |
Installation