Table 1.2 AC OUTPUT WIRING AND BREAKERS
Item
(Column 1)
Rated AC Output
Current in In-
verter Mode
(Column 2)
NEC Ampacity =
125% of Column
2
(Column 3)
Wire Size based on NEC
Ampacity at Column 3
and 75°C Copper Conduc-
tor in Conduit
(Column 4)
Breaker Size
(Based on NEC Am-
pacity at Column 3)
(Column 5)
EVO-2212
18.33A
22.91
AWG #10
25A
EVO-2224
18.33A
22.91
AWG #10
25A
EVO-3012
25A
31.25
AWG #8
35A
EVO-4024
33.33A
41.66
AWG #8
45A
TABLE 1.3(a) BATTERY CABLES IN FREE AIR AND EXTERNAL BATTERY SIDE FUSES
Item
Copper, 90°C
Fuse
Up to 5 ft.
Up to 10 ft.
EVO-2212
AWG #3/0
AWG #4/0
350A
EVO-2224
AWG #2
AWG #2
175A
EVO-3012
2 X AWG #3/0 (MCM 300)
2 X AWG #3/0 (MCM 300)
500A
EVO-4024
AWG #3/0
AWG #4/0
350A
External Charger
AWG #6
AWG #2
70A
TABLE 1.3 (B) BATTERY CABLES IN RACEWAY AND EXTERNAL BATTERY SIDE FUSES
Item
Copper, 90°C
Fuse
Up to 5 ft.
Up to 10 ft.
EVO-2212
2 X AWG #4/0 (MCM 350)
2 X AWG #4/0 (MCM 350)
350A
EVO-2224
AWG #1/0
AWG #1/0
175A
EVO-3012
Not recommended
Not recommended
500A
EVO-4024
2 X AWG #4/0 (MCM 350)
2 X AWG #4/0 (MCM 350)
300A
External Charger
AWG #6
AWG #2
70A
TABLE 1.4 TIGHTENING TORQUES
Battery Input
Connectors
External Charger Input
Connectors
AC Input and Output
Connectors
70 kgf.cm
(5.0 lbf.ft)
35 kgf.cm
(2.5 lbf.ft)
7 to 12 kgf.cm
(0.5 to 0.9 lbf.ft)