Installation Instruction, Installation Manual, Installation Manual, Installation Manual, User Manual, User Manual, Installation Manual, Applications Manual, Installation Manual, Applications Manual, Installation Manual, Applications Manual, Safety Manual, Marine Installation Manual, Installation Manual, Installation Manual
of
47
Modbus installation
vacon • 14
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
4
5
Using the cable clamp included in the delivery of the drive, ground the shield of
the RS485 cable to the frame of the AC drive.
6
If Vacon 100 is the last device on the bus
, the bus termination must be set.
Locate the DIP switches to the right of the control keypad of the drive and turn
the switch for the RS485 bus termination resistor to position ON. Biasing is built
in the termination resistor. See also step 9 on page 15.
Cable clamp
RS485*
AO1
AI1
AI2
OFF
ON
Current
Voltage
Current
Voltage
Current
Voltage
* Bus termination resistor