Vacon 100 INDUSTRIAL Installation And User Manual - page 46
Annex
vacon • 44
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
9
9.
A
NNEX
Process Data IN (Master to Slave)
Use of Process Data In variables depends on the used application. The configuration of the data
is free.
Process Data OUT (Slave to Master)
Use of Process Data Out variables depends on the used application.
The Fieldbus Master can read the frequency converter’s actual values using process data vari-
ables. Control applications use process data as follows:
Table 31. Process Data OUT variables
ID
Data
Value
Unit
Scale
2104
Process data OUT 1
Output Frequency
Hz
0,01 Hz
2105
Process data OUT 2
Motor Speed
rpm
1 rpm
2106
Process data OUT 3
Motor Current
A
0,1 A
2107
Process data OUT 4
Motor Torque
%
0,1 %
2108
Process data OUT 5
Motor Power
%
0,1 %
2109
Process data OUT 6
Motor Voltage
V
0,1 V
2110
Process data OUT 7
DC link voltage
V
1 V
2111
Process data OUT 8
Active Fault Code
-
-