DALI principles for the DLR/S
ABB Stotz Kontakt GmbH currently has 4 KNX-DALI devices in the ABB i-bus
®
KNX range, for the
integration of DALI interfaces in a KNX building installation. Independent of additional functions such as
constant light control, every device has its strengths, which become obvious with the different project
types.
The following table shows the fundamental technical differences between the DALI controls. This manual
deals primarily with group-oriented DALI control that is supported in the DLR/S. A detailed description of
the DALI Gateway DG/S specific functions can be found in the product manuals of the DALI Gateway.
Property
DG/S 8.1
Central
control
DG/S 1.1
Individual
control
DG/S 1.16.1
Group
control
DGN/S 1.16.1
Group
control
DLR/S 8.16.1M
Group
control
DLR/A 4.8.1.1
Group
control
Design
MDRC
MDRC
MDRC
MDRC
MDRC
SM
Mounting width
(1 space unit = 18 mm)
6 units
4 units
4 units
4 units
6 units
220 x 147 x 50 mm
DALI outputs
8 (A…H)
2 (A, B)
1 (A)
1 (A)
1 (A)
1 (A)
Light Sensor (LF/U 2.1)
inputs
-
-
-
-
8
4
DALI equipment (ballast) per
gateway (IEC62386-101)
128 (max. 16 per
output)
128 (max. 64 per
output)
64
64 (ballasts and
emergency lighting
converter)
64
64
DALI emergency lighting
converter (IEC62386-202)
-
-
-
64
-
-
Lighting groups per Gateway 8 (installation)
A: max. 255 (KNX)
B: 1
16
1)
(DALI)
16 (DALI)
16 (DALI)
8 (DALI)
Lighting groups
established via
cable installation
A: KNX
B: Cable
installation
DALI
DALI
DALI
DALI
DALI devices (e.g. ballasts)
per lighting group
max. 16
A: 64 max.
B: 64 max.
max. 64
max. 64
max. 64
max. 64
DALI addressing
not required
A: 64 Individual
B: 64 individual
64 individual
64 individual
64 individual
64 individual
Number of DALI telegrams
per KNX telegram of the
group
1 telegram
A: max. 64
telegrams
B: 1 telegram
1 telegram per
group
1 telegram per
group
1 telegram per
group
1 telegram per
group
Power supply to KNX
processor
2)
via
KNX
KNX
KNX
KNX
KNX
KNX
DALI voltage
3)
integrated power
supply
integrated power
supply
integrated power
supply
integrated power
supply
integrated power
supply
integrated power
supply
1)
Overlapping DALI groups are supported, i.e. a DALI device may belong to several DALI groups.
2)
KNX programming is possible when KNX voltage is connected. Gateway operating voltage for KNX programming is not
required.
3)