ABB i-bus KNX Product Manual - page 148
ABB i-bus
KNX
Commissioning
146 2CDC 507 100 D0202 | DLR/S 8.16.1M
No.
Function
Object name
Data type
Flags
33
Status Brightness value
Group x
1 bit
DPT 5.001
C, R, T
This communication object is enabled if, in the
, page 77, the parameter Status response of
brightness value is set with the Yes: via separate object "Brightness value/Status" option.
Telegram value:
0 = OFF
…
255 = 100 %, max. brightness value
This communication object reports back the current brightness value of the lighting group. The value of the communication
object updates itself during a dimming process, staircase lighting time curve or scene sequence.
It is possible to parameterize when a status telegram is sent. The status can be sent After a change and/or After request.
34
Relative dimming
Group x
1 bit
DPT 3.007
C, W
The relative dimming telegram is received for the respective lighting group via this communication object. They are the
dimming telegrams BRIGHTER, DARKER and STOP. After a START telegram is received, the brightness value is changed
in the defined direction with the parameterized speed. If a STOP telegram is received before the dim process ends or the
maximum or minimum dimming value is reached, the dimming process is interrupted and the received brightness value is
retained.
If the dimming values are above or below the max. or min. dimming values (dimming thresholds), the respective dimming
threshold is set. If the dimming values are above or below the max. or min. dimming values (dimming thresholds), the
respective dimming threshold is set.
This communication object is not available with a parameterized additional function.
Due to the DALI functionality (dimming step 200 ms), the "Step-by-step dimming" rarely used in KNX is only conditionally
supported.
In addition to the control telegrams and status responses of the lighting groups, there is the possibility to
set the fault status for the lighting group on the KNX via a separate communication object for every lighting
group.