ABB i-bus KNX Product Manual - page 15
ABB i-bus
KNX
Device technology
DLR/S 8.16.1M | 2CDC 507 100 D0202 13
Operating and display elements
Button/LED
For assignment of the physical address
Button
/LED
For switchover between manual operation and
KNX operation
Button
Switch to next lighting group
Button
Switch ON or dim UP
Button
Switch OFF or dim DOWN
Button
Detect devices
LED
Display for operation readiness
LED
DALI operating voltage display
16 LED
…
Lighting group
1…16 display
Degree of protection
IP 54
Compliant to EN 60 529
Protection class
II
Compliant to EN 61 140
Isolation category
Overvoltage category
Pollution degree
III to EN 60 664-1
2 to EN 60 664-1
KNX safety extra low voltage
SELV 24 V DC
DALI voltage
Typical 16 V DC (9.5…22.5 V DC)
No-load voltage
Lowest supply current at 11.5 V
Highest supply current
To DIN EN 60 929 and DIN EN 62 386
16 V DC
4)
160 mA
230 mA
Temperature range
Power
-
5 °C…+45 °C
Storage
-
25…+55 °C
Transport
-
25…+70 °C
Environmental conditions
Humidity
Maximum 95 %, no condensation allowed
Design
Modular installation device (MDRC)
Modular installation device, ProM
Dimensions
90 x 108 x 64.5 mm (H x W x D)
Mounting width
6 x 18 mm modules
Mounting depth
68 mm
Mounting
On 35 mm mounting rail
Compliant to EN 60 715
Installation position
Any
Weight
0.26 kg
Housing, color
Plastic housing, gray
Approvals
KNX to EN 50 090-1, -2
EN 62 386 (Part 101 and 102)
Certification
DALI
CE mark
In accordance with the EMC guideline and low
voltage guideline
1)
Maximum load corresponds to 64 DALI devices at 2 mA each.
2)
The length relates to the entire routed DALI control cable.
The maximum values are rounded off and relate to the resistance value. EMC influences are not considered. For this reason, the values should be
considered as absolute maximum values.
3)
Rooms are lit up differently by the incidental daylight and the artificial light of the lamps. Not all the surfaces in the rooms, e.g. walls, floor and
furniture, reflect the light which falls on them in the same manner. Accordingly, even though there is an exactly calibrated constant light control in
daily operation, deviations to the setpoint value may occur. These deviations may be up to +/- 100 lx, should the current ambient conditions in the
room, and accordingly the reflection properties of the surfaces (paper, people, reorganized or new furniture), differ significantly from the original
ambient conditions at the time of calibration. Deviations may also occur if the light sensor is influenced by direct or reflected light falling on it, which
is not influenced or only slightly influenced by the surfaces in the detection range of the light sensor.
4)
Cannot be measured directly on the digital multimeter, as there is not a constant DC voltage due to the DALI telegrams. Measure with a CRO for
correct results. One exception is the KNX download phase. In this phase, no DALI telegrams are sent, whereby the DALI voltage is constantly
present on the DALI output.