The reaction of the Slave function after KNX voltage recovery can be parameterized: In the
, page 112, you can set whether operation is active or inactive. The brightness value of
the lighting group after KNX voltage recovery can be set in the
If the Active mode is parameterized, the parameterized brightness value is initially set after KNX voltage
recovery. Subsequently, the next brightness value received via communication object Brightness value of
Slave is then set.
In the following table, the response to received telegrams with the parameterized Slave function is shown.
Operating situation
or
Communication objects
Additional function Slave
Inactive
(Function Activate Slave = 0)
Active in standby
(Activate slave mode = 1)
Active and ON (running)
(Function = 1)
Download (start)Download
(start)
Such as KNX bus voltage failure
Download (end)
Such as KNX bus voltage recovery
KNX bus
Voltage failure
Parameterizable:- Brightness value - Gx Fault
Voltage
recovery
Programmable:
- Mode: - Gx Slave
- Brightness value - Gx Fault
DALI
or
Gateway
operation
Voltage failure
Programmable:
- Brightness value - Gx Fault
Voltage
recovery
Programmable:
- Mode: - Gx Slave
- Brightness value - Gx Fault
Switch
ON
Switch-on value
→ Active,
current Brightness value of slave is
set
Programmable:
- No reaction
- Goes to standby and sets
switch-on value
OFF
OFF
OFF, remains in standby
OFF and goes to standby
Relative dimming
Dimming
Dimming, remains in standby
Programmable:
- No reaction
- Goes to standby and dims
Brightness value
Brightness value
Brightness value, remains in standby
Programmable:
- No reaction
- Goes to standby and sets
brightness value
Brightness value of slave
No reaction
No reaction
Brightness value of slave
is set
Slave function
activate
0
No reaction
→ Inactive
→ Inactive
1
Current
brightness value of slave
→ Active
Current
brightness value of slave
→ Active
Current
brightness value of slave
Recall scene
Scene
Scene
Programmable:
- No reaction
- Goes to standby and starts
scene