ABB i-bus KNX Product Manual - page 14
ABB i-bus
KNX
Device technology
12 2CDC 507 100 D0202 | DLR/S 8.16.1M
2.1
DLR/S 8.16.1M
2.1.1
Technical data DLR/S 8.16.1M
Supply
Light controller supply voltage
85…265 V AC, 50/60 Hz
110…240 V DC
Power consumption total via mains
Maximum 3.5 W at 230 V AC and max. load
1)
Current consumption total via mains
Maximum 15 mA at 230 V AC and max. load
1)
Leakage loss total for device
Maximum 1.6 W at 230 V AC and max. load
1)
Current consumption KNX
Maximum 10 mA
Power consumption via KNX
Maximum 210 mW
DALI output
Number of outputs
1 to EN 60 929 and DIN EN 62 386
The DALI output is a fixed 230 V, i.e.
unintentional application of the light controller
supply voltage will not cause destruction of the
DALI output.
Number of DALI devices
Maximum 64
Number of lighting groups
16
Distance between DLR/S and last DALI device
Cable cross-section
0.50 mm
2
0.75 mm
2
1.00 mm
2
1.50 mm
2
100 m
2)
150 m
2)
200 m
2)
300 m
2)
Sensor inputs
Light Sensor LF/U 2.1
Number of inputs
Max. cable length per sensor
For detailed information,
see
8
Per light sensor 100 m, Ø 0.8 mm,
P-YCYM or J-Y(ST)Y cable (SELV),
e.g. shielded KNX bus cable
Connections
KNX
KNX connection terminal,
0.8 mm Ø, solid
DALI outputs and mains voltage
Screw terminal:
0.2…2.5 m
m2
fine stranded
0.2…4 mm
2
single core
Tightening torque
Max. 0.6 Nm
Light Sensor LF/U:
Wire end ferrule without/with plastic sleeve
TWIN ferrule
Tightening torque
Without 0.25…2.5 mm
2
/ with 0.25…4 mm
2
0.5…2.5 mm
2
Max. 0.6 Nm
Brightness detection
Lighting control operating range
Optimized for 500 Lux.
200…1,200 Lux for rooms with average
furnishing level, degree of reflection 0.5
Max. 860 Lux in a very brightly furnished room
(reflection 0.7)
Max. 3,000 Lux in a very darkly furnished room
(reflection 0.2)
The Lux values are measured values on the
work surface (reference surface)
3)
.