ABB i-bus KNX Product Manual - page 188
ABB i-bus
KNX
Planning and application
186 2CDC 507 100 D0202 | DLR/S 8.16.1M
In order to get a point of reference for the individual control parameterization, in the following table, you will
find a list of the fixed parameterized settings in the DLR/S, as well as the individually adjustable values for
the Changing brightness during lighting control (fast
1
), medium, slow and the individual setting):
Changing brightness during light control
(correction speed)
Fast
Medium
Slow
Individual
setting
Step time for fast approach [0.1 s…2.0 s]I
As quickly as
possible.
0.5
1
1
Step time for slow approach [1 s…10 s]
2
3
4
4
Setpoint/actual difference, for changeover of fast/slow
approach
[0…50]
20
20
20
20
Maximum increment size of a control step [1…10]
1
1
1
1
Setpoint/actual difference, up to which control is with
max. step width
[10…255]
30
30
30
30
Deviation actual value from nominal
value for starting controlling [0...30]
1
1
1
1
1)
The selection fast is only possible if the light controller does not control any further slaves via the communication object
Master brightness value. The setting is made in parameter window - Gx Light controller with the parameter Light controller
controls other dimmer actuators as "master" other dimmer actuators).