ABB i-bus KNX Product Manual - page 124
ABB i-bus
KNX
Commissioning
122 2CDC 507 100 D0202 | DLR/S 8.16.1M
3.3.1
Summary of communication objects
CO No.
Function
Name
Data Point
Type (DPT)
Length
Flags
C
R
W T
U
0
In operation
General
1.002
1 bit
x
x
1
Block manual operation/Status
General
1.003
1 bit
x
x
x
x
2
Trigger DALI addressing
General
1.003
1 bit
x
x
3
Status Additional functions
General
non
2 byte
x
x
x
4
Fault controller supply
General
1.005
1 bit
x
x
x
5
Acknowledge fault message
General
1.015
1 bit
x
x
6
Diagnostics
General
non
2 byte
x
x
x
7
Request Diagnostics
General
non
1 bit
x
x
8
Fade time (DALI format)
General
non
1 byte
x
x
x
x
8
Fade time (KNX format)
General
7.004
2 byte
x
x
x
x
9
Status Sensors
General
non
1 byte
x
x
x
10
Request status values
General
1.017
1 bit
x
x
11
Switch
DALI output
1.001
1 bit
x
x
Switch/Status
DALI output
1.001
1 bit
x
x
x
x
12
Status Switch
DALI output
1.001
1 bit
x
x
x
13
Brightness value
DALI output
5.001
1 byte
x
x
Brightness value/Status
DALI output
5.001
1 byte
x
x
x
x
14
Status Brightness value
DALI output
5.001
1 byte
x
x
x
15
Relative dimming
DALI output
3.007
4 bit
x
x
16
Lamp fault
DALI output
1.005
1 bit
x
x
x
17
Ballast fault
DALI output
1.005
1 bit
x
x
x
18
Fault DALI
DALI output
1.005
1 bit
x
x
x
19
Fault group/device code
DALI output
non
1 byte
x
x
x
20
Number of faults
DALI output
5.010
1 byte
x
x
x
21
No. Group/device fault
DALI output
5.010
1 byte
x
x
x
22
Switch up next fault message
DALI output
1.008
1 bit
x
x
23
Disabel send. of fault message
DALI output
1.003
1 bit
x
x
24
Conflict DALI
DALI output
1.005
1 bit
x
x
x
25
Detect devices
DALI output
1.010
1 bit
x
x
26
Burn-in lamp
DALI output
1.010
1 bit
x
x
x
x
Burn-in lamp/Status
DALI output
1.010
1 bit
x
x
x
x
27
Enable controller calibration
DALI output
non
1 byte
x
x
x
28
Calibration artificial light
DALI output
1.003
1 bit
x
x
29
Calibration daylight
DALI output
1.003
1 bit
x
x