ABB i-bus KNX Product Manual - page 46
ABB i-bus
KNX
Commissioning
44 2CDC 507 100 D0202 | DLR/S 8.16.1M
Function of manual operation
After connection to the KNX, the device is in KNX mode. The LED is off. All the LEDs display the
current input state. The respective buttons are non-functional. It is possible to switch between KNX
operation and Manual operation by pressing the
button.
During manual operation, the states received via the KNX are executed. The manually set states
are retained if manual operation is deactivated.
Switching on manual operation:
Press the
button until the yellow LED lights continuously.
Switching off manual operation:
Press the
button until the LED is no longer lit.
Note
If the
button is released again before 1.5 seconds have elapsed, the LED reverts to its old
state and there is no reaction.
If manual operation is disabled via the application, there is no reaction and the device remains in
the KNX mode.
If manual operation has been enabled, the LED is switched on or over, after it has flashed for
1.5 seconds.
For further information see:
page 28
Time for automatic reset of
manual operation in s [100...6000]
Options:
100…300…6000
This parameter is enabled if manual operation is enabled. It specifies for how long the device
remains in manual operation after the
button is pressed and after the last manual operation in
the Manual operation operating state.
The automatic reset is performed after the last manual operation and after the set time has elapsed.