ABB i-bus KNX Product Manual - page 129
ABB i-bus
KNX
Commissioning
DLR/S 8.16.1M | 2CDC 507 100 D0202 127
No.
Function
Object name
Data type
Flags
Continuation of no. 6
The bit number (bit 0 to bit 15) corresponds to the exponent in the binary system, e.g. bit 8, number 8 corresponds to 2
8
.
Bit 0...5:
Corresponds to the information as queried in the communication object Request Diagnostics (no. 7).
The content identifies the DALI device or the lighting group for which information has been
requested.
Bit 6:
Determines if a group (value 1) or an individual device (value 0) has been recalled
Bit 7:
Contains a 0
Bit 8…15:
Contains the following coded information concerning the recalled DALI device or recalled lighting
group
Bit 8:
Lamp fault:
Value 0 = No fault
Value 1 = Fault
Bit 9:
Ballast fault:
Value 0 = No fault
Value 1 = Fault
Bit 10:
Status of the device monitoring:
Value 0 = There is no monitoring (the DALI devices are not considered with the
monitoring of the ballast)
Value 1 = Monitoring available
Bit 11:
Status of Burn-in function
Value 0 = Burn-in function not activated
Value 1 = Burn-in function activated (device or lighting group)
can only assume state OFF and 100 %
Bit 12:
Status of additional function, Slave, Light control:
Value 0 = No additional function for the device or the lighting group is
activated
Value 1 = The additional function for the device or the lighting group is
activated
Bit 13:
Block status:
Value 0 = Lighting group is not disabled
Value 1 = Lighting group is disabled
Bit 14:
Status Forced operation:
Value 0 = Lighting group is not forcibly operated
Value 1 = Lighting group is forcibly operated
Bit 15
Status disable sending of fault alarm: (by group, if selected)
Value 0 = Fault message is not disabled
Value 1 = Fault message is disabled
Device available: (by device, if selected)
Value 0 = Device available
Value 1 = Device not available
This information is independent of whether the device is no longer responding
because of an error, or is completely unavailable.
After a KNX bus voltage recovery (Power On) on the DLR/S, this communication object receives the value FF FF Hex.
After a download or light controller supply voltage failure, the previous value recalled after the KNX bus voltage recovery
remains in the communication object.
For further information see: