ABB i-bus KNX Product Manual - page 152
ABB i-bus
KNX
Commissioning
150 2CDC 507 100 D0202 | DLR/S 8.16.1M
3.3.5
Communication objects Scene x/y
The 8 bit scene communication object is always available. The communication objects for the 1 bit control
of a scene are only visible when the respective scene has been enabled in the
page 117. Enabling is always in pairs.
In the
, page 118, it is possible to parameterize which lighting group is a
member of the scene.
Note
The Staircase lighting function is comprised of two scenes. The DLR/S automatically selects the internal
scenes 13 and 14 when the Staircase lighting function is selected.
For further information see:
No.
Function
Object name
Data type
Flags
212
8-bit scene
Scene 1…14
1 byte
DPT 18.001
C, W
This communication object is always enabled.
Using this 8 bit communication object, a scene telegram can be sent using a coded telegram which integrates the lighting
groups in a KNX scene. The telegram contains the number of the respective scene as well as the information whether the
scene is to be retrieved, or if the brightness values in the scene are to be assigned to the lighting group in the scene.
Telegram values (1 byte): M0SS SSSS
(MSB) (LSB)
M: 0 = scene is recalled
1 = Scene is stored (if allowed)
S: Number of the scene (1…13: 00000000…00001101)
KNX 8 bit telegram value
Meaning
Decimal
Hexadecimal
00
01
02
…
13
00h
01h
02h
…
0Hh
Recall scene 1
Recall scene 2
Recall scene 3
…
Recall scene 14
128
129
130
…
141
80h
81h
82h
…
8Dh
Store scene 1
Store scene 2
Store scene 3
…
Store scene 14
Other numeric values do not affect the communication objects Store scene or Recall scene.
For further information, see: