KEB COMBIVERT F5 Instructions For Use Manual - 4 Unit Data
4 Unit data
Information on the dimensioning are contained in chapter
Unit size
14
16
18
20
22
Housing size
E
G
H
R
R
Cooling mode (L=air; W=water)
L
L
L
L
L
W
Input data
Phases
3
Permitted mains forms
TN system
1)
Input rated voltage
U
N
Vac
400
Input voltage range
U
in
Vac
340…480 ± 0%
Mains frequency
f
N
Hz
50 / 60 ±2
Input rated power
S
N
kVA
11
23
35
52
80
Input rated current
I
N
Aac 16.5
33
50
75
2)
115
2)
Max. permissible mains fuse type gR / aR
A
25
50
80
100
160
Output data
Rated output voltage
U
outN
Vdc
680
Output voltage range
U
Vdc
530…840
3)
Overvoltage switch-off (E.OP)
U
OP
Vdc
840
Power supply-/regenerative rated current 4)
I
outN
Adc 16.5
33
50
75
115
Max. regenerative DC current 30 s
I
outmax
Adc 29.7
49.5
75
112
172
207
Rated switching frequency
5)
f
SN
kHz
8
Max. switching frequency
f
Smax
kHz
16
Other data (referring to the rated data)
Overcurrent cut-off E.OC
I
OC
%
216
180
180
180
180
216
Over load current (E.OL) 30 s
I
OL
%
180
150
150
150
150
180
Max. permissible DC link capacity
C
ext
mF
–
–
–
50
50
I
AFE
A
29
6)
57
29
226
226
Max. external charging current (=>
)
I
ext
A
75
6)
135
322
–
–
Max. permissible total charging current (=>
)
I
pre
A
104
6)
192
351
226
226
Type
A1
A2
A1
D1
Permissible DC fuses
see chapter
Short-circuit factor at the connection point (S
mains
/S
N
)
15
kn
“
Power dissipation at nominal operating
W
295
449
525
830
1400
Max. heat sink temperature
°C
90
90
90
90
90
60
Table 7:
Unit data
1)
Operation on a local limited IT system with sinus EMC filter is possible.
2)
The input current of the drive converter is limited, if necessary to the rated current of the AFE / LCL filter.
3)
The operation is dependent on the voltage setpoint and the U
OP
limit (see
).
4)
Measured at a reference voltage of 680 Vdc.
5)
Must be set to 8 kHz for AFE operation (factory setting 4 kHz) !
6)
At ambient temperature Ta of 45°C.
27
UNIT DATA