KEB COMBIVERT F5 Instructions For Use Manual - 5 Installation
5 Installation
5.1 EMC-compatible control cabinet installation
1a
Mains fuse
150 mm
30 mm
150 mm
1a
5a
2a
2b
6
7
9b
8
9c
9a
10
10a
11
5
3
4
1b
150 mm
1b
Precharging fuse
2a
Pre-charging contactor
2b
Main contactor (before LCL filter)
3
EMC filter
4
AFE/LCL filter (if necessary integrat
-
ed in 4)
5
COMBIVERT F5-AFE
5a
If necessary external load-shunt
6
External DC fuses
7
Drive converter
8
Motor line
9a
Power unit equipotential bonding
with the housing earth
9b
Protective Earth (PE) on the mount-
ing plate power circuit
9c
Protective Earth (PE) on the mount-
ing plate control circuit
10
Mains connection power circuit
10 A Mains connection control circuit
11
Control lines
Large area contact at the mounting
plate
Control circuit
Power circuit
Direction of the
cooling fins
Table 14:
EMC-compatible control cabinet installation
5.2 Installation instructions
• Stationarily install and earth COMBIVERT.
• Take care to prevent foreign material, dust, mist or water getting into the unit.
•
Allow for sufficient heat dissipation if installed in a dust-proof housing.
• Install the COMBIVERT in an appropriate housing in accordance with the local reg-
ulations when operating it in explosion-endangered spaces.
• Protect COMBIVERT against conductive and aggressive gases and liquids.
•
The AFE/LCL filter must be placed in the immediate environment of the AFE.
• The drive converters must be placed in the immediate environment of the AFE.
• The DC connection lines must be kept as short as possible.
• The use of ferrite on the DC line is not permitted.
34
INSTALLATION