Installation Manual, Instruction Manual, Instruction Manual, Instructions For Use Manual, Instructions For Use Manual, Instruction manual, Installation Manual, Instruction Manual, Instruction Manual, Instruction Manual, Instructions For Use Manual, Instruction Manual, Instruction Manual, Safety Manual, Instruction Manual, Instruction Manual, Instruction Manual, Instruction Manual, Instructions for use manual, Instruction Manual, Instruction Manual, Instruction Manual, Instruction Manual, Instruction Manual, Installation Manual, Instruction Manual
Manual is about: ELEVATOR DRIVE
of
72
ATTENTION
The maximum temperature difference between pre-run and return flow
is specified in the technical data and should not be exceeded. If the vol
-
ume flow (above 30 l / min per module) is selected too large, increases
the risk of erosion in the liquid cooler.
11.1.5.3
Volume flow in dependence of the heat power dissipation and temperature difference
Pv
in kW
ΔT in K
0
1
2
3
4
5
6
7
8
9
10
11
12
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Legend
Master / Slave / Slave 9-12 ΔT in K
②
15 l/min
Master / Slave 6-10 ΔT in K
③
20 l/min
Master 3-6 ΔT in K
④
25 l/min
①
10 l/min
⑤
30 l/min
Figure 23: Volume flow in dependence of the heat power dissipation
68
COOLING SySTEM