KEB COMBIVERT F5 Instructions For Use Manual - page 37
Housing size P
U
V
W
+PA
-
PB
L1
L2
L3
PE
PE
PE
PE
T1T2
K1K2
max.42,5 mm
Terminal
strip
Name
Function
Terminal
X1A
L1, L2, L3
3-phase mains connection
12
U, V, W
AFE mains connection
+PA, PB
Connection for braking resistor
+PA, –
Connection for DC interconnection
X1D
T1, T2
Connection for temperature sensor (only master)
8
K1, K2
GTR7 monitoring (only water-cooled units)
X1A
PE,
Connection for protective earth
12
No.
Permissible cross-section flexible with wire-end ferrule
Tightening torque
mm²
AWG
Nm
lb inch
min
max
min
max
1
0.25
4
24
10
0.6
5
2
0.25
1.5
26
14
0.6
5
3
Screw M4 for ring thimble
1.3
11
4
6
16
22
8
1.2
11
5
2.5
35
12
2
4.5
40
6
0.5
2.5
21
12
0.6
6
7
16
50
6 AWG
0 MCM
12…15
120
8
0.2
4
24 AWG
10 AWG
0.6
5.3
9
10 mm stay bolt for ring thimble
25
220
10
50
150
1/0 AWG
300 MCM
25…30
270
11
10 mm stay bolt for ring thimble and for DC connection
50-150qmm
25
220
12
12 mm stay bolt for ring thimble
max. 2 ring thimbles with 240 mm² for each
35
310
37
CONNECTION OF THE COMbIVERT F5-AFE