Jablotron JA-63 „PROFI“ Installation Manual - page 13
JA-63 „PROFI“ Alarm System
- 13 -
MGK51404
•
Arming control of the subsystem by the master control panel can be disabled by erasing the corresponding cN position in
the sub-control panel. For example if the master control panel was enrolled to position c3, scroll to this position in the
enrolling mode and holding key 2 will erase the master control panel as a controller.
10.11 Enrollment of the control panel to a UC-2xx or to a master control panel
sequence: 2 9 9
The wireless control panel can send data to output modules UC–216, UC–222 and UC-260 (see section 21). It can also
work as a subsystem of another JA-6x.
Enter the enrolling mode of the UC receiving device and then enter 299 on the control panel. Note that the control panel
must be in the programming mode. This enables the control panel to generate the enrollment signal.
If you want to enroll a subsystem to your control panel, enter the enrolling mode on the MASTER control panel (see
10.1.) and then enter sequence 299 in the programming mode of the sub control panel.
If the system is split, the sub control panel enrolls to the common shared section.
10.12 No code requested for
,
,
,
(F1, F2, F3), F4, F8 & F9
sequence: 3 0 x
If this parameter is enabled, no code is requested for the functions listed above. When this parameter is disabled, these
functions (keys) can be used only when followed by a code (Master or User) – see the following table:
function / setting
301
300
arming
„code“
partial arming
„code“
door opening
„code“
memory reading
F 4
F 4 „code“
appliance control
F80, F81
F8 “code” 0
F8 “code” 1
message listening
F 9
F 9 „code“
„code“ = Master or User
Factory default setting: no code requested
Note: this feature is also selectable on the JA-60D wireless keypad and it is independent from the control panel setting.
10.13 Partial (Home) arming with
- non split control panel
sequence: 3 1 x
In partial arming, the control panel reacts only to detectors addressed to section A (see 10.2 and 10.25) and it ignores
the triggering of detectors in section B or C (except smoke and gas detectors). Partial arming can be disabled with this
sequence.
options:
3 1 1 partial
arming
enabled
3 1 0
partial arming disabled
Factory default setting: partial arming enabled
10.14 Hard wired siren alarm enabled
sequence: 3 2 x
The SIR siren output is activated when any alarm is triggered (except silent Panic alarm). This siren indication can be
disabled with this parameter.
options:
3 2 1 siren
enabled
3 2 0 siren
disabled
Factory default setting: siren enabled
10.15 Exit delay audible indication
sequence: 3 3 x
The exit delay can be indicated by the “beeping“ of the keypad (for the last five seconds, the beeping is faster). The
audible indication can be disabled with this setting.
options:
3 3 1 indication
enabled
3 3 0 indication
disabled