Jablotron JA-63 „PROFI“ Installation Manual - page 21
JA-63 „PROFI“ Alarm System
- 21 -
MGK51404
13.1 Reaction to an incoming call
sequence: 05
This sequence sets how the communicator will react to incoming calls on the telephone line. This setting is important for
remote access.
0 5 x
x can be 0 - never answer
1 - answer after second call = after 1 or 2 rings are detected, there must be a pause of 10 - 45
seconds. The dialer will then answer on the very first ring of the second call. This setting can be
used to bypass an answering or facsimile machine connected to the same line. This “Second
Call” feature is supported by the Comlink software and also by the JA-60E keypad.
2 to 6 - answer after 2
nd
to 6
th
ring
Notes: Remote access connection can also be enabled by the alarm system user (regardless of the above setting) by entering 89
while in the user mode, when the phone rings. If you use another telephone set on the same telephone line, it should be switched to
the tone dial mode.
Factory setting: 0 = never answer
13.2 Remote access code setting
sequence: 07
In order to access the panel remotely, it is necessary to authorize the access with an 8-digit access code. This code is
compared with the one programmed in the control panel. If the caller tries to access the panel with an other code, the
connection will be terminated immediately. A wrong code alarm will be triggered on the control panel after the 5
th
unsuccessful attempt to dial in. Store your access code to the control panel by entering:
0 7 xxxxxxxx
x x . . . . . x - any 8 digits access code
Factory setting: 00000000
14 Central monitoring station communication setting
This part of the manual is intended only for specialists involved in monitoring. We recommend to use a computer
equipped with Comlink program for complete setting of the monitoring station communication (see 17). Changes of the
setting can also be performed manually using the keypad:
• Enter programming mode when disarmed (F 0 Service Code, factory default 6060), indicated by a “P“.
• To exit programming press the N key (“P“ will turn off).
Central monitoring station communication parameters
Sequence Description
Factory
default
setting
0 001 xx
to
0 198 xx
Reporting codes table (see part 16)
where: x= 0 – 9, F0 = A
h
, F1 = B
h
, F2 = C
h
, F3 = D
h
, F4 = E
h
, F5 = F
h
if 00 is set, the event is not reported
00
For all events
0 2 xxxx
Account ID code (4 digits, for 3/1 and 3/2 formats the structure is 0xxx)
x = 0 – 9 (hexadecimal codes can be used too - see above)
0000
0 3 xy
Protocol x:
0 = Ademco Slow
1 = Ademco Fast
2 = Telemax
3 = Franklin
4 =Radionics 2300
5 = Radionics 1400
6 = DTMF 2300
7 = Surgard
8 = Ademco Express
9 = Contact ID
Format y:
0 = 3/1 (xxx R)
1 = 3/2 (xxx rc)
2 = 4/1/1 (xxxx Rn)
3 = 4/2 (xxxx rc)
90
Contact ID
0 4 x
Re-dialing pause, x= 1 – 9 (x 10 min.)
1 10
minutes
0 6 xx..xFy
CMS phone numbers xx...x to memory y (1 and 2), pause = F0
erased
0 9 6060
Communicator reset to factory default settings
Dialing method ( tone / pulse) and telephone line checking has a common setting with the voice & SMS message setting - see parts 12.5 and 12.6.
Notes:
Some of the protocols are not standardized
and some manufacturers of Monitoring Station
receivers use different parameters in some of
their protocols. Therefore Jablotron cannot
guarantee full compatibility with all Central
Monitoring Station receivers.
If the connection with the Monitoring Station is
not available, the events are queued in the
communicator’s memory and are transmitted in
one burst as soon as the connection is
established. All events are reported to the
Monitoring Station in the same order as they
happened.
Once communication has started, it can not
be interrupted unless the control panel is
switched to the programming or to the user
mode. For example, if the user causes a false
alarm and then cancels it, both events are sent
to Monitoring Station.
Events occurring while the control panel is
in the programming or user mode are reported
to the Monitoring Station after the closing of
these modes. (They are stored in the memory
and reported together with reporting codes
describing the change of operation modes.)
When the dialer is activated, the
communication to the monitoring station has
the highest priority (voice and SMS messages
are sent later with lower priority). A User or
Installer can interrupt the digital dialer
communication by entering the User mode or
Programming mode. Reset of the control panel
has no influence to the digital communicator’s
settings (it is reported to the Monitoring station
as an event).
The RESET of the digital communicator
itself (sequence 0 9 6060), the change of the
Monitoring Station’s telephone numbers, the
change of an account number code or the
change of a format setting will erase all the
reporting codes queued in the communicator’s
memory. However the events remain stored in
the control panel’s internal memory.
Jablotron recommends use of the MS-300
monitoring station with ComGuard SW.