Jablotron JA-63 „PROFI“ Installation Manual - page 6
JA-63 „PROFI“ Alarm System
- 6 -
MGK51404
5 Terminals and connectors on the main board
There is a Digital data jack for the JA-60E keypad(s) and/or for a PC interface cable. The same connecter is also
available on the bottom right corner of the control panel housing. The digital bus signals are also available on terminals
1234.
1,2,3,4 digital data terminals provide an option to use standard
cable for the wiring of JA-60E keypads.
Up to four JA-60E keypads can be wired to the control panel
(connected in parallel). The total length of the keypad cables should
not exceed 100m. If using the jack connectors, the data cable length
should not exceed 10 meters. Use ordinary twisted pair cable
connected to the 1234 terminals for longer distance.
AC20V – output of the power transformer (20VAC) is connected to
this pair of terminals.
L1,L2, L3, L4 – hard wired zone inputs – detector outputs can be
wired here: see examples of wiring on page 7. For each input it is
possible to program its method of triggering: Normally Closed loop,
balanced loop (2k2) or double balanced loop (2x 1k1) and the type
of reaction of the system (see section 10.2).
Factory default setting: all inputs are triggered as balanced loops,
reactions: L1= delay, L2= next delay, L3= instant a L4= tamper
COM common terminal to close (balance) the input
NO
is a normally open contact of the alarm output relay.
NC
is a normally closed contact of the alarm output relay.
C
is a common contact of the alarm output relay, max. load 60V /
1A. The relay is turned on during any alarm.
SIR
is an external siren output. In the normal mode it has a +U
terminal voltage. In the alarm mode it has a GND terminal potential.
Connect an ordinary external siren to +U and SIR terminals (max. load
0,7 A). A two wires back up siren should be connected to the GND and
the SIR terminals (during an alarm, the charging will temporarily halt).
The siren can also be used for arming and disarming chirps and as an
audible indicator while in the testing mode (see section 10.18).
PGX, PGY are outputs (switching to GND when activated, max. 12V, 100mA). The function of these outputs are determined by
the setting in the programming mode (see 10.5). The control panel also wirelessly transmits the PGX and PGY
signals and UC receiving units can be used as remote outputs for these signals.
+U
is a back up power output for external items (detectors etc.). The max. permanent current is 0.4A (1.2 A for max. 15
min - not more then one cycle per hour). This output is fused (FU2 1.6A) and supervised by the control panel. If it is
overloaded, a control panel failure will be indicated (fault C).
GND
is a common ground terminal for power output (-).
RADIO
MODULE
JA-63R