3-2 Basic Installation
MN1941
3.1.2 Mounting the NextMove e100
Before touching the unit be sure to discharge static electricity from your body and
clothing by touching a grounded metal surface. Alternatively, wear an earth strap
while handling the unit.
Ensure you have read and understood the location requirements in section 3.1.1. Mount the
NextMove e100 using the supplied M4 screws. For effective cooling, the NextMove e100 must
be mounted on a smooth non-flammable vertical surface. Orientation must be as shown in
Figure 1, with the two slots in the metal carrier / heat sink assembly at the bottom.
140
(5
.51)
129
(5
.08)
170 (6.69)
250 (9.84)
All dimensions shown as
mm (inches)
40.3
(1
.59)
Mounting keyhole and slot detail
A
B
C
A 4.5 mm
B 10 mm
C 11 mm
A
Drawings not to scale
Figure 1 - Package dimensions
There must be at least 20 mm (0.8 in) clearance between the NextMove e100 and neighboring
equipment to allow sufficient cooling by natural convection. Remember to allow additional space
around the edges to accommodate the mating connectors and associated wiring. For example,
70 mm (2.8 in) clearance will be required for connection of the serial port cable.
NOTICE