Baldor NXE100-1608Dx Installation manual - page 28
www.baldormotion.com
4-12 Input / Output
MN1941
4.3.2.3 DOUT12 (relay) connections
The relay connections are available on connector X12, as shown in section 4.1.1. The relay
outputs are isolated from any internal circuits in the NextMove e100. In normal operation, while
there is no error, the relay is energized and REL COM is connected to REL NO. In the event of
an error or power loss, the relay is de-energized, and REL COM is connected to REL NC. For
control purposes the relay is considered to be another digital output (DOUT12), and can be
controlled directly using the Mint OUT or OUTX keywords. The relay can be configured as the
global error output by setting GLOBALERROROUTPUT to 12. See the Mint help file.
Relay
REL COM
REL NC
REL NO
7
9
‘X12’
8
Mint
GLOBALERROROUTPUT
or
DRIVEENABLEOUTPUT
+5 V
NextMove e100
Figure 16 - Relay connections