Vacon 100 INDUSTRIAL Applications Manual - page 21
3
vacon • 19
VACON HVAC Drive Application
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
3.2
Example of control connections
Table 10. Connection example, basic I/O board
Basic I/O board
Terminal
Signal
Default
1
+10 Vref
Reference output
2
AI1+
Analogue input,
voltage or current
*
*
Selectable with DIP switches, see Vacon 100 Installa-
tion Manual
Voltage
3
AI1-
Analogue input common
(current)
4
AI2+
Analogue input,
voltage or current
Current
5
AI2-
Analogue input common
(current)
6
24Vout
24V aux. voltage
7
GND
I/O ground
8
DI1
Digital input 1
Start FWD
9
DI2
Digital input 2
10
DI3
Digital input 3
Fault
11
CM
Common A for DIN1-DIN6
12
24Vout
24V aux. voltage
13
GND
I/O ground
14
DI4
Digital input 4
Preset
freq select
1
15
DI5
Digital input 5
Preset
freq select
2
16
DI6
Digital input 6
Fault reset
17
CM
Common A for DIN1-DIN6
18
AO1+
Analogue signal (+output)
OP freq
19
AO-/GND
Analogue output common
30
+24 Vin
24V auxiliary input voltage
A
RS485
Differential receiver/trans-
mitter
B
RS485
Differential receiver/trans-
mitter
Reference potentiometer
1...10 k
Ω
Remote reference
4...20mA/0...10V
(programmable)
mA
To Relay board
1 or 2
Remote control
ground