Installation Instruction, Installation Manual, Installation Manual, Installation Manual, User Manual, User Manual, Installation Manual, Installation Manual, Applications Manual, Installation Manual, Installation And User Manual, Applications Manual, Safety Manual, Marine Installation Manual, Installation Manual, Installation Manual
of
78
VACON HVAC Drive Application
vacon • 64
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
3
PRESSURE LOSS COMPENSATION
Figure 16. Position of pressure sensor
If pressurizing a long pipe with many outlets, the best place for the sensor would probably be
halfway down the pipe (Position 2). However, sensors might, for example, be placed directly af-
ter the pump. This will give the right pressure directly after the pump, but farther down in the
pipe the pressure will drop depending on the flow.
Pressure
No flow
Pipe length
PT
PT
Position 1
Position 2