Vacon 100 INDUSTRIAL Applications Manual - page 73
3
vacon • 71
VACON HVAC Drive Application
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
3.7
HVAC Application - Fault tracing
When an unusual operating condition is detected by the AC drive control diagnostics, the drive
initiates a notification visible, for example, on the keypad. The keypad will show the code, the
name and a short description of the fault or alarm.
The notifications vary in consequence and required action.
Faults
make the drive stop and re-
quire reset of the drive.
Alarms
inform of unusual operating conditions but the drive will con-
tinue running.
Infos
may require resetting but do not affect the functioning of the drive.
For some faults you can program different responses in the application. See parameter group
Protections.
The fault can be reset with the
Reset button
on the control keypad or via the I/O terminal. The
faults are stored in the Fault history menu which can be browsed. The different fault codes you
will find in the table below.
NOTE: When contacting distributor or factory because of a fault condition, always write down
all texts and codes on the keypad display.
3.7.1
Fault appears
When a fault appears and the drive stops examine the cause of fault, perform the actions ad-
vised here and reset the fault either
1.
with a long (1 s) press on the
Reset
button on the keypad or
2.
by entering the
Diagnostics
Menu (M4), entering
Reset faults
(M4.2) and selecting
Reset
faults
parameter.
STOP
READY
I/O
Main Menu
Main Menu
( 5 )
Monitor
Parameters
( 12 )
Diagnostics
( 6 )
M4
ID:
STOP
READY
I/O
Diagnostics
Active faults
( 0 )
Reset faults
Fault history
( 39 )
M4.1
ID:
STOP
READY
I/O
Reset faults
Reset faults
Help
M4.2
ID:
OK