Vacon 100 INDUSTRIAL Applications Manual - page 31
Other manuals for 100 INDUSTRIAL:
Installation Instruction, Installation Manual, Installation Manual, Installation Manual, User Manual, User Manual, Installation Manual, Installation Manual, Applications Manual, Installation Manual, Installation And User Manual, Applications Manual, Safety Manual, Marine Installation Manual, Installation Manual, Installation Manual
of
78
3
vacon • 29
VACON HVAC Drive Application
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
3.5.4
Group 3.2: Start/Stop setup
Table 22. Start/Stop Setup menu
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.2.1
Remote control
place
0
1
0
172
Selection of remote control
place (start/stop)
0=I/O control
1=Fieldbus control
P3.2.2
Keypad stop button
0
1
0
114
0=Stop button always
enabled (Yes)
1=Limited function of Stop
button (No)
P3.2.3
Start function
0
1
0
505
0=Ramping
1=(Conditional) flying start
P3.2.4
0
1
0
506
0=Coasting
1=Ramping
P3.2.5
0
2
0
300
CtrlSgn 1
CrtlSgn 2
0 Start fwd
Start fwd
1 Start fwd
Stop pulse
pulse
(3-wire)
2 Start fwd pulse
P3.2.6
I/O B start/stop
logic
0
2
0
363
See above.
P3.2.8
Fieldbus start logic
0
1
0
889
0=Rising edge required
1=State