Vacon 100 INDUSTRIAL Applications Manual - page 44
VACON HVAC Drive Application
vacon • 42
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
3
3.5.11
Group 3.10: Automatic reset
Table 34. Autoreset settings
Code
Parameter
Min
Max
Unit
Default
ID
Description
3.10.1
0
1
0
731
0 = Disabled
1 = Enabled
3.10.2
Restart function
0
1
1
719
The start mode for Automatic
reset is selected with this
parameter:
0 = Flying start (conditional)
1 = According to par. P3.2.3
3.10.3
Wait time
0,10
10000,0
s
0,50
717
Wait time before the first
reset is executed.
3.10.4
0,00
10000,0
s
60,00
718
When the trial time has
elapsed, and the fault is still
active, the drive will trip to
fault.
3.10.5
Number of trials
1
10
4
759
NOTE: Total number of trials
(irrespective of fault type)
3.10.6
Autoreset:
Undervoltage
0
1
1
720
Autoreset permitted?
0 = No
1 = Yes
3.10.7
Autoreset:
Overvoltage
0
1
1
721
Autoreset permitted?
0 = No
1 = Yes
3.10.8
Autoreset:
Overcurrent
0
1
1
722
Autoreset permitted?
0 = No
1 = Yes
3.10.9
Autoreset: AI low
0
1
1
723
Autoreset permitted?
0 = No
1 = Yes
3.10.10
Autoreset: Unit over-
temperature
0
1
1
724
Autoreset permitted?
0 = No
1 = Yes
3.10.11
Autoreset: Motor over-
temperature
0
1
1
725
Autoreset permitted?
0 = No
1 = Yes
3.10.12
Autoreset:
External fault
0
1
0
726
Autoreset permitted?
0 = No
1 = Yes