Vacon 100 INDUSTRIAL Applications Manual - page 50
VACON HVAC Drive Application
vacon • 48
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
3
3.5.13.3
Feedbacks
Table 38.
Code
Parameter
Min
Max
Unit
Default
ID
Description
P3.12.3.1
Feedback function
1
9
1
333
1=Only Source1 in use
2=SQRT(Source1);(Flow=Con
stant x SQRT(Pressure))
3= SQRT(Source1- Source 2)
4= SQRT(Source 1) + SQRT
(Source 2)
5= Source 1 + Source 2
6= Source 1 - Source 2
7=MIN (Source 1, Source 2)
8=MAX (Source 1, Source 2)
9=MEAN (Source 1, Source 2)
P3.12.3.2 Feedback function gain
-1000.0
1000.0
%
100.0
1058
Used e.g. with selection 2 in
Feedback function
P3.12.3.3
Feedback 1
source selection
0
14
1
334
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = AI5
6 = AI6
7 = ProcessDataIn1
8 = ProcessDataIn2
9 = ProcessDataIn3
10 = ProcessDataIn4
11 = ProcessDataIn5
12 = ProcessDataIn6
13 = ProcessDataIn7
14 = ProcessDataIn8
AI’s and ProcessDataIn are
handled as % (0.00-100.00%)
and scaled according to
Feedback min and max.
NOTE: ProcessDataIn use
two decimals.
P3.12.3.4
Feedback 1 minimum
-200.00
200.00
%
0.00
336
Minimum value at analogue
signal minimum.
P3.12.3.5
Feedback 1 maximum
-200.00
200.00
%
100.00
337
Maximum value at analogue
signal maximum.
P3.12.3.6
Feedback 2
source selection
0
14
0
335
See P3.12.3.3
P3.12.3.7
Feedback 2 minimum
-200.00
200.00
%
0.00
338
Minimum value at analogue
signal minimum.
P3.12.3.8
Feedback 2 maximum
-200.00
200.00
%
100.00
339
Maximum value at analogue
signal maximum.