VACON HVAC Drive Application
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
3.3
HVAC Application - Quick setup parameter group
The Quick Setup parameter group is a collection of parameters that are most commonly used
during installation and commissioning. They are collected in the first parameter group so that
they can be found fast and easily. They can, however, be also reached and edited in their actual
parameter groups. Changing a parameter value in the Quick setup group also changes the val-
ue of this parameter in its actual group.
Table 13. Quick setup parameter group
Code
Parameter
Min
Max
Unit
Default
ID
Description
1.1
Motor nominal voltage
180.0
690.0
V
230.0
110
Find this value U
n
on the
rating plate of the motor.
1.2
Motor nominal fre-
quency
0.00
320.00
Hz
50.00
111
Find this value f
n
on the rat-
ing plate of the motor. See
1.3
Motor nominal speed
0
19200
rpm
1420
112
Find this value n
n
on the rat-
ing plate of the motor.
1.4
Motor nominal current
0
Varies
A
Varies
113
Find this value I
n
on the rat-
ing plate of the motor.
1.5
Motor Cos Phi
0.00
1.00
0.80
120
Find this value on the rating
plate of the motor
1.6
Motor nominal power
0.00
Varies
kW
1.50
116
Find this value I
n
on the rat-
ing plate of the motor.
1.7
Motor current limit
Varies
Varies
A
Varies
107
Maximum motor current
from AC drive
1.8
Minimum frequency
0.00
50.00
Hz
Varies
101
Minimum allowed fre-
quency reference
1.9
Maximum frequency
20.00
320.00
Hz
50.00
102
Maximum allowed frequency
reference
1.10
I/O control reference A
selection
1
7
6
117
Selection of ref source when
control place is I/O A. See
page 30 for selections.
1.11
P3.3.1
P3.3.2
Hz
10.00
105
Select with digital input:
Preset frequency selection
1.12
P3.3.1
P3.3.2
Hz
15.00
106
Select with digital input:
Preset frequency selection
1.13
Acceleration time
0.1
3000.0
s
20.0
103
Time to accelerate from zero
to maximum frequency
1.14
Deceleration time
0.1
3000.0
s
20.0
104
Time to decelerate from
minimum to zero frequency
1.15
Remote control place
1
2
1
172
Selection of remote control
place (start/stop)
1 = I/O
2 = Fieldbus
1.16
Automatic reset
0
1
0
731
0 = Disabled
1 = Enabled
1.17
PID Mini-Wizard
0
1
0
0 = Inactive
1 = Active
See chapter 1.2.