Samlexpower EVO-2212E Owner's Manual - Section 4 |
24 | SAMLEX AMERICA INC.
SAMLEX AMERICA INC. | 25
APPENDIX A
SECtION 4 |
Parameter Setup
FLoAtinG eXit:
Please refer to Sections 5.6.4 and 5.8 of the EVO Owner's Manual regarding automatic resetting of 3
and 4 Stage Charging Cycles respectively. When charging is in Float Stage and the battery discharges
to the programmed discharged voltage level, the Charging Cycle is reset to the Bulk Stage of the 3
Stage Charging Profile. The programmable range of this voltage level is 10 to 13V for 12V battery and
20 to 26V for 24V battery and the Default Setting is 12V for 12V battery and 24V for 24V battery.
SELECT GROUP
CHARGE CURVE
CHARGE CURVE
BULK CURRENT
FLOATING EXIT
12.00V
Enter Key
ò
Up Key x 14
ò
GS Detect tiMe
This parameter is a Programmable Timer (0-600sec; Default: 10 sec) that is used for pro-
gramming On-Line / Off Line UPS Modes (Section 4.4) and Automatic Starting and Stopping
of Generator (Section 4.8 under “Relay Function”). The Timer sets the duration the battery
voltage has to remain at threshold of “LOW VOLT ALARM” condition [(i) for 12V: 9.5V –
12.5V / Default 11.0V (ii) for 24V: 19.0V – 25.0V / Default 22.0V], or lower before the fol-
lowing actions are initiated:
• Automatic Starting and Stopping of Generator: Switching ON (energizing) the
Status Relay to initiate Generator starting
• on-Line Mode: Switching ON of the Transfer Relay to transfer from “Inverting” Mode
to “Charging” Mode
SELECT GROUP
CHARGE CURVE
CHARGE CURVE
BULK CURRENT
GS DETECT TIME
10 sec
Enter Key
ò
Up Key x 15
ò
Gen on tiMe
This parameter is a Programmable Timer (0-240min; Default: 60 min) that is used for program-
ming Automatic Starting and Stopping of Generator (Section 4.8 under “Relay Function”:
4=Generator 2). The Timer sets the duration the Generator will remain ON from the time the
Status Relay has been switched ON (energized). The Status Relay will switch ON (energize) and
start the Generator if the battery voltage remains at threshold of “LOW VOLT ALARM” condi-
tion [(i) for 12V: 9.5V – 12.5V / Default 11.0V (ii) for 24V: 19.0V – 25.0V / Default 22.0V], or
lower for continuous period = “GS DETECT TIME” (0 – 600sec; Default 10 sec)
SELECT GROUP
CHARGE CURVE
CHARGE CURVE
BULK CURRENT
GEN ON TIME
60 min
Enter Key
ò
Up Key x 16
ò
Gen oFF tiMe
This parameter is a Programmable Timer (0-240min; Default: 60 min) that is used for the following:
• ProgrammingAutomaticStartingandStoppingofGenerator(Section4.8under“Relay
Function”: 3=Generator 1). The Timer sets the time period the batteries are required
to remain charged at the desired programmed level of voltage = “RESET VOLTAGE” [(i)
for 12V: 12.0V – 17.0V / Default 14.0V (ii) for 24V: 24.0V – 35.0V / Default 28.0V], or
higher before the Status Relay is switched OFF (de-energized) to stop the Generator.
• ProgrammingOption2inOn-Line/OffLineUPSModes(Section4.4:1=Option2).The
Timer sets the time period the batteries are required to remain charged at the desired