APPENDIX A
SECtION 4 |
Parameter Setup
programmed level of voltage = “RESET VOLTAGE” [(i) for 12V: 12.0V – 17.0V / Default
14.0V (ii) for 24V: 24.0V – 35.0V / Default 28.0V], or higher before the Transfer Relay is
switched OFF (de-energized) to exit “Charging” Mode and revert to “Inverting” Mode .
SELECT GROUP
CHARGE CURVE
CHARGE CURVE
BULK CURRENT
GEN OFF TIME
60 min
Enter Key
ò
Up Key x 17
ò
4.5 GRoUP 2 PARAMeteR Set UP: inPUt SettinG
Please refer to Parameters under Group 2 at Fig 4.1. Details of Parameter set up are given below:
tABLe 4.5. GRoUP 2 PARAMeteR Set UP: inPUt SettinG
Page
no. for
Group
2 (Fig
4.1)
Parameter
Setting range
Default value
eVo-
2212
eVo-
3012
eVo-
2224
eVo-
4024
eVo-
2212
eVo-
3012
eVo-
2224
eVo-
4024
1
DeFAULt FReQ
0=60Hz;1=50Hz
0=60Hz
2
GRiD MAX cURRent
5 – 40A 5 – 70A 5 – 40A
5 – 70A
30A
3
Gen MAX cURRent
5 – 40A 5 – 70A 5 – 40A
5 – 70A
30A
4
HiGH cUt oFF
50–70Hz
65Hz
5
HiGH ReSet
50–70Hz
64Hz
6
LoW cUt oFF
40–60Hz
55Hz
7
LoW ReSet
40–60Hz
56Hz
DeFAULt FReQ:
Default frequency sets the Inverter frequency, which is also the standard frequency for AC input.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT SETTING
DEFAUT FREQ
0= 60Hz
Up Key
ò
Enter Key
ò
GRiD MAX cURRent / Gen MAX cURRent:
In Charging Mode, the net AC input current from the Grid/Generator is the sum of the AC
side charging current and the pass through load current. Based on the rated capacity of the
Grid Branch Circuit/Generator, the net AC input current will be required to be limited to
prevent overloading of the Grid Branch Circuit/Generator.
EVO Series has a very powerful battery charger that will require a proportionate higher
AC input current from the Grid/Generator. The Grid/Branch Circuit/Generator will also be
required to provide current to the AC loads. The desired maximum value of input current
from Grid/Generator can be programmed (Default is 30A). The EVO will automatically reduce
charging current to support the AC loads on priority and use whatever is extra for charging.
This will prevent overloading of the Grid Branch Circuit/Generator. If the AC input current is
over the setting value by 1A for 5 seconds, the EVO Inverter Charger will stop outputting and
display an error message “Input over current!” on LCD screen.