tAble 6.3 ProgrAmmAble AnD DefAult PArAmeterS - grouP "inPut Setting"
group
Parameter
name
Programming range
Default value
EVO-
2212
EVO-
3012
EVO-
2224
EVO-
4024
EVO-
2212
EVO-
3012
EVO-
2224
EVO-
4024
inPut
Setting
DefAult freQ
0 = 60hz
1 = 50hz
0 = 60hz
griD mAX
current
5 – 40A 5 – 70A 5 – 40A 5 – 70A
30A
gen mAX
current
5 – 40A 5 – 70A 5 – 40A 5 – 70A
30A
high cut off
50 – 70hz
65hz
high reSet
50 – 70hz
64hz
low cut off
40 – 60hz
55hz
low reSet
40 – 60hz
56hz
tAble 6.4 ProgrAmmAble AnD DefAult PArAmeterS - grouP "inPut low limit"
group
Parameter name
Setting range
Default value
EVO-
2212
EVO-
3012
EVO-
2224
EVO-
4024
EVO-
2212
EVO-
3012
EVO-
2224
EVO-
4024
inPut -
low limit
reSet voltAge
60.0 – 100.0V
95.0V
cut off Point 1
60.0 – 100.0V
90.0V
Detect time 1
0 – 2000 cycle
300 cycle
cut off Point 2
60.0 – 100.0V
85.0V
Detect time 2
0 – 2000 cycle
60 cycle
cut off Point 3
60.0 – 100.0V
80.0V
Detect time 3
0 – 2000 cycle
1 cycle
tAble 6.5 ProgrAmmAble AnD DefAult PArAmeterS - grouP "inPut high limit"
group
Parameter name
Setting range
Default value
EVO-
2212
EVO-
3012
EVO-
2224
EVO-
4024
EVO-
2212
EVO-
3012
EVO-
2224
EVO-
4024
inPut -
high limit
reSet voltAge
100.0 – 150.0V
135.0V
cut off Point 1
100.0 – 150.0V
140.0V
Detect time 1
0 – 2000 cycle
300 cycle
cut off Point 2
100.0 – 150.0V
145.0V
Detect time 2
0 – 2000 cycle
60 cycle
cut off Point 3
100.0 – 150.0V
150.0V
Detect time 3
0 – 2000 cycle
1 cycle
SECTIOn 6 |