Samlexpower EVO-2212E Owner's Manual - Section 3 |
46 | SAMLEX AMErICA INC.
Stripped Wire End
Wire End Terminal
Crimp barrel Portion
↓
→
Insert the terminated end of the wire fully into the terminal slot till it stops. Tighten the screw
firmly. Tightening torque for the screws – 7 to 12 Kgf*cm / 0.5 to 0.9 lbf*ft.
fig 3.11 Stripped wire end terminal on Ac wiring
3.7.2 tightening torques
Tightening torques to be applied to the wiring terminals are given in Table below:
tightening torQueS
battery input
connectors
external charger input
connectors
Ac input and output
connectors
70 kgf.cm
(5.0 lbf.ft)
35 kgf.cm
(2.5 lbf.ft)
7 to 12 kgf.cm
(0.5 to 0.9 lbf.ft)
3.8 SiZing of wiring AnD breAKerS - Ac inPut SiDe
wArning!
AC breakers for the AC input circuits have NOT been provided internally. These have to be
provided externally by the installer / user based on guidelines given below. Please note that
guidelines given below on wire sizing and over-current protection will be superseded by the
applicable National / Local Electrical Codes.
Attention!
Breakers AC pour les circuits d’entrée AC ont pas été fournis en interne. Ceux-ci doivent être fournies à l’extérieur par
l’installateur / utilisateur sur la base des directives données ci-dessous. Se il vous plaît noter que les directives ci-dessous
sur dimensionnement des câbles et protection contre les surintensités seront remplacées par les nationaux / codes
électriques locaux applicables.
3.8.1 tables for wire and breaker Sizing - Ac input Side
Tables 3.2.1 to 3.2.3 provide details of wire and breaker sizing for the AC input side.
table 3.2.1: for EVO-2212, 2224, 3012 and 4024 for AC Input Current Limit ("GrID
MAX CurrENT" / "GEN MAX CurrENT") set at 30A (Default Setting)
table 3.2.2: for EVO-2212, 2224, 3012 and 4024 for full rated AC input currents.