Samlexpower EVO-2212E Owner's Manual - Section 3 |
48 | SAMLEX AMErICA INC.
i
info for table 3.2.1 (column 8)
AC input breaker size of 40A (Column 8) and corresponding AC input wire size of
AWG #8 (Column 7) for all the 4 models is based on the default AC input current limit
of 30A (Column 7). The AC input current limit in EVO is a programmable parameter
specified as "GrID MAX CurrENT" and "GEN MAX CurrENT" (see Section 4.5 of
Owner's Manual for remote Control EVO-rC at Appendix - A). The 30A default AC
input current has been used to match the standard 30A mains power inlet plug (using
30A cord) on motorhomes / rVs.
for using the full rated AC input current capacities of the 4 models (Column 4), higher
AC input current limits ("GrID MAX CurrENT" / "GEN MAX CurrENT") will have to
be programmed using the optional remote Control Model EVO-rC. AC input breakers
and AC input wiring sizes will also change. In this regard, please refer to Table 3.2.2.
tAble 3.2.2 SiZing of griD AnD generAtor inPut wiring AnD breAKerS for full rAteD
Ac inPut currentS for evo-2212, evo-2224, evo-3012, evo-4024
model no. and
rated output
Power in in-
verter mode
(column 1)
rated
Ac Pass
through
current
(See note
1)
(column 2)
rated Ac
charging
current
(See note
2)
(column 3)
total rated
Ac input
current
(columns
2 +3)
(See note 3)
(column 4)
Pro-
grammed
Ac input
current
limit
[griD mAX
current/
gen mAX
current]
(See note 4)
(column 5)
nec Ampac-
ity = 125% of
column 5
(See note 5)
(column 6)
conductor
Size based
on nec
Ampacity at
column 6
(See note 6)
(column 7)
external
breaker
Size
based
on nec
Ampacity at
column 6
(See note 7)
(column 8)
EVO-2212
(2200VA, 18A)
18 A
15A
33A
33A
41.25A
AWG #8
45A
EVO-2224
(2200VA, 18A)
18A
19A
37A
37A
46.25A
AWG #8
50A
EVO-3012
(3000VA, 25A)
25A
20A
45A
45A
56.25A
AWG #6
60A
EVO-4024
(4000VA, 33A)
33A
29A
62A
62A
77.5A
AWG #4 or
2X AWG #6
80A
noteS for tAbleS 3.2.1 AnD 3.2.2 - SiZing of griD AnD generAtor inPut
wiring AnD breAKerS
1) Column 2 indicates the rated AC Pass Through Current when in Charger / Pass
Through Mode (value of this current = rated AC Output Current in Inverter Mode).
2) Column 3 indicates the rated AC Side Charging Current in Charger / Pass Through
Mode.
3) Column 4 indicates the total rated AC Input Current which is the sum of the rated
AC Pass Through Current (Column 2) and the rated AC Side Charging Current
(Column 3).