Samlexpower EVO-2212E Owner's Manual - Section 4 |
28 | SAMLEX AMERICA INC.
SAMLEX AMERICA INC. | 29
APPENDIX A
Detect tiMe 2:
This is the time limit in cycles up to which low AC input voltage "CUT-OFF 2" is allowed.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT LOW LIMIT
DETECT TIME 2
60 cycles
RESET VOLTAGE
95.0 V
Up Key x 2
ò
Enter Key
ò
Up Key x 4
ò
cUt oFF VoLt 3:
If during "Charging Mode", the AC input voltage falls below "CUT-OFF VOLT 3" for period >
"DETECT TIME 3", the EVO Inverter Charger will transfer to "Inverting Mode".
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT LOW LIMIT
CUT OFF VOLT 3
80.0 V
RESET VOLTAGE
95.0 V
Up Key x 2
ò
Enter Key
ò
Up Key x 5
ò
Detect tiMe 3:
This is the time limit in cycles up to which the low AC input voltage "CUT-OFF 3" is allowed.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT LOW LIMIT
DETECT TIME 3
1 cycle
RESET VOLTAGE
95.0 V
Up Key x 2
ò
Enter Key
ò
Up Key x 6
ò
4.7 GRoUP 4 PARAMeteR Set UP: inPUt HiGH LiMit
Please refer to Parameters under Group 4 at Fig 4.1. Details of Parameter set up are given below:
tABLe 4.7. GRoUP 4 PARAMeteR Set UP: inPUt HiGH LiMit
Page
no. for
Group 4
(Fig 4.1)
Parameter
Setting range
Default value
eVo-
2212
eVo-
3012
eVo-
2224
eVo-
4024
eVo-
2212
eVo-
3012
eVo-
2224
eVo-
4024
1
ReSet VoLtAGe
100.0 – 150.0V
135.0V
2
cUt oFF VoLt 1
100.0 – 150.0V
140.0V
3
Detect tiMe 1
0 – 2000 cycles
60 cycles
4
cUt oFF VoLt 2
100.0 – 150.0V
145.0V
5
Detect tiMe 2
0 – 2000 cycles
15 cycles
6
cUt oFF VoLt 3
100.0 – 150.0V
150.0V
7
Detect tiMe 3
0 – 2000 cycles
1 cycle
ReSet VoLtAGe:
This is the reset voltage at which the unit will revert to "Charging Mode" after it has switched
over to "Inverting Mode" due to input AC voltage rising to "CUT-OFF VOLT 1/CUT-OFF VOLT 2/
CUT-OFF VOLT 3.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT HIGH LIMIT
RESET VOLTAGE
135.0 V
Up Key x 3
ò
Enter Key
ò