Samlexpower EVO-2212E Owner's Manual - Section 4 |
28 | SAMLEX AMERICA INC.
APPENDIX A
SECtION 4 |
Parameter Setup
4.6 GRoUP 3 PARAMeteR Set UP: inPUt LoW LiMit
Please refer to Parameters under Group 3 at Fig 4.1. Details of Parameter set up are given below:
tABLe 4.6. GRoUP 3 PARAMeteR Set UP: inPUt LoW LiMit
Page
no. for
Group
3 (Fig
4.1)
Parameter
Setting range
Default value
eVo-
2212
eVo-
3012
eVo-
2224
eVo-
4024
eVo-
2212
eVo-
3012
eVo-
2224
eVo-
4024
1
ReSet VoLtAGe
60.0 – 100.0V
95.0V
2
cUt oFF VoLt 1
60.0 – 100.0V
90.0V
3
Detect tiMe 1
0 – 2000 cycles
300 cycles
4
cUt oFF VoLt 2
60.0 – 100.0V
85.0V
5
Detect tiMe 2
0 – 2000 cycles
60 cycles
6
cUt oFF VoLt 3
60.0 – 100.0V
80.0V
7
Detect tiMe 3
0 – 2000 cycles
1 cycle
ReSet VoLtAGe:
This is the reset voltage at which the unit will revert to "Charging Mode" after it has
switched over to "Inverting Mode" due to input voltage falling to "CUT-OFF VOLT 1/CUT-OFF
VOLT 2/CUT-OFF VOLT3".
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT LOW LIMIT
RESET VOLTAGE
95.0 V
Up Key x 2
ò
Enter Key
ò
cUt oFF VoLt 1:
If during "Charging Mode", the AC input voltage falls below "CUT-OFF VOLT 1" for period >
"DETECT TIME 1", the EVO Inverter Charger will transfer to Inverting Mode from "Charging
Mode".
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT LOW LIMIT
CUT OFF VOLT 1
90.0 V
RESET VOLTAGE
95.0 V
Up Key x 2
ò
Enter Key
ò
Up Key x 1
ò
Detect tiMe 1:
This is the time limit in cycles up to which low AC input voltage "CUT-OFF VOLT 1" is allowed.
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT LOW LIMIT
DETECT TIME 1
300 cycles
RESET VOLTAGE
95.0 V
Up Key x 2
ò
Enter Key
ò
Up Key x 2
ò
cUt oFF VoLt 2:
If during "Charging Mode", the AC input voltage falls below "CUT-OFF VOLT 2" for period >
"DETECT TIME 2", the EVO Inverter Charger will transfer to "Inverting Mode".
SELECT GROUP
CHARGE CURVE
SELECT GROUP
INPUT LOW LIMIT
CUT OFF VOLT 2
85.0 V
RESET VOLTAGE
95.0 V
Up Key x 2
ò
Enter Key
ò
Up Key x 3
ò