3.9.1 tables for wire and breaker Sizing - Ac output Side
Table 3.3 provides details of wire and breaker sizing for the AC output side.
AC wiring and breaker sizes on the AC output side are required to be determined by the
rated Load Current when operating in Inverter Mode (Column 1).
table 3.3
SiZing of Ac outPut wiring AnD breAKerS
item model no.
and
rated output
Power in inverter
mode
(column 1)
rated Ac out-
put current in
inverter mode
(See note 1)
(column 2)
nec Ampac-
ity = 125%
of column 2
(See note 2)
(column 3)
conductor Size
based on nec
Ampacity at
column 3
(See note 3)
(column 4)
external breaker
Size based on
nec Ampacity at
column 3
(See note 3)
(column 5)
EVO-2212
(2200VA, 18A)
18.33A
22.91
AWG #10
25A
EVO-2224
(2200VA, 18A)
18.33A
22.91
AWG #10
25A
EVO-3012
(3000VA, 25A)
25A
31.25
AWG #8
35A
EVO-4024
(4000VA, 33A)
33.33A
41.66
AWG #8
45A
noteS for tAble 3.3 - Ac outPut wiring AnD breAKerS
1) Column 2 indicates the rated AC Output Current in Inverter Mode
2) Column 3 indicates NEC Ampacity based on which the output-wiring conductor
is sized. This NEC Ampacity is not less than 125% of the rated Output Current in
Inverter Mode (Column 2). - refer to NEC-2014 (National Electrical Code) - Section
215.2(A)(1)(a) regarding feeder Circuit Conductors. PLEASE NOTE that when the
unit is operating in Inverter Mode, it is considered to be an AC source that is feeding
power to the Load Center / breaker Panel on the load side. hence, the AC output
circuit of the unit is considered to be a feeder Circuit for purposes of NEC-2014.
3) Column 4 indicates conductor size for the output side wiring. The size is based on
NEC-2014 (National Electrical Code) - Ampacity Table 310.15(b)(16) for raceway.
Conductor size is based on (i) NEC Ampacity (Column 3), (ii) conductor temperature
of 75°C and (iii) ambient temperature of 30°C / 86°f.