Samlexpower EVO-2212E Owner's Manual - Section 4 |
30 | SAMLEX AMERICA INC.
SAMLEX AMERICA INC. | 31
APPENDIX A
4.8 GRoUP 5 PARAMeteR Set UP: otHeR FUnctionS
Please refer to Parameters under Group 5 at Fig 4.2. Details of Parameter set up are given below:
tABLe 4.8. GRoUP 5 PARAMeteR Set UP: otHeR FUnctionS
Page
no. for
Group 5
(Fig 4.2)
Parameter
Setting range
Default value
eVo-
2212
eVo-
3012
eVo-
2224
eVo-
4024
eVo-
2212
eVo-
3012
eVo-
2224
eVo-
4024
1
PoWeR SAVinG
1 = Enable 0 = Disable
1 = Enable
2
enteR Point
4 – 50W
6W
8W
6W
8W
3
WAKe UP Point
5 – 50W
7W
10W
7W
10W
4
ReMote SWitcH
0 = Button Type
1 = Switch Type
Button type
5
ReLAY FUnction
0 = Charge/Other
1 = Normal/Fault
2 = Generator 0
3 = Generator 1
4 = Generator 2
2 = Generator 0
6
coMM iD
1 – 255
1
7
BUZZeR
1 = ON
0 = OFF
1 = ON
8
DiScHARGe BeeP
1 = ON
0 = OFF
0 = OFF
9
DeFAULt ReSet
0 = No
1 = Yes
0 = No
10
DAtALoG DiSABLe
DAtALoG tiMe
0 = Disable, 1 = 1 sec,
2 = 10 sec, 3 = 30 sec
4 = 1 min, 5 = 5 min, 6 = 10 min
1 = 1 sec
11
PARAMeteR SAVe
0 = No
1 = Yes
0 = No
PoWeR SAVinG:
Enable or disable Power Saving Mode when in "Inverting Mode".
SELECT GROUP
CHARGE CURVE
SELECT GROUP
OTHER FUNCTION
POWER SAVING
1 = Enable
Up Key x 4
ò
Enter Key
ò
enteR Point:
If the value of power drawn by AC load falls to the "ENTER POINT" value for 5 sec, the unit
will enter "Power Save Mode".
SELECT GROUP
CHARGE CURVE
SELECT GROUP
OTHER FUNCTION
ENTER POINT
6W / 8W
POWER SAVING
1 = Enable
Up Key x 4
ò
Enter Key
ò
Up Key x 1
ò