Samlexpower EVO-2212E Owner's Manual - Section 1 |
6 | SAMLEX AMErICA INC.
table 1.2 Ac outPut wiring AnD breAKerS
item
(column 1)
rated Ac output
current in in-
verter mode
(column 2)
nec Ampacity =
125% of column
2
(column 3)
wire Size based on nec
Ampacity at column 3
and 75°c copper conduc-
tor in conduit
(column 4)
breaker Size
(based on nec Am-
pacity at column 3)
(column 5)
evo-2212
18.33A
22.91
AWG #10
25A
evo-2224
18.33A
22.91
AWG #10
25A
evo-3012
25A
31.25
AWG #8
35A
evo-4024
33.33A
41.66
AWG #8
45A
tAble 1.3(a) bAttery cAbleS in free Air AnD eXternAl bAttery SiDe fuSeS
item
copper, 90°c
fuse
up to 5 ft.
up to 10 ft.
evo-2212
AWG #3/0
AWG #4/0
350A
evo-2224
AWG #2
AWG #2
175A
evo-3012
2 X AWG #3/0 (MCM 300)
2 X AWG #3/0 (MCM 300)
500A
evo-4024
AWG #3/0
AWG #4/0
350A
external charger
AWG #6
AWG #2
70A
tAble 1.3 (b) bAttery cAbleS in rAcewAy AnD eXternAl bAttery SiDe fuSeS
item
copper, 90°c
fuse
up to 5 ft.
up to 10 ft.
evo-2212
2 X AWG #4/0 (MCM 350)
2 X AWG #4/0 (MCM 350)
350A
evo-2224
AWG #1/0
AWG #1/0
175A
evo-3012
Not recommended
Not recommended
500A
evo-4024
2 X AWG #4/0 (MCM 350)
2 X AWG #4/0 (MCM 350)
300A
external charger
AWG #6
AWG #2
70A
tAble 1.4 tightening torQueS
battery input
connectors
external charger input
connectors
Ac input and output
connectors
70 kgf.cm
(5.0 lbf.ft)
35 kgf.cm
(2.5 lbf.ft)
7 to 12 kgf.cm
(0.5 to 0.9 lbf.ft)
SECTIOn 1 |
Safety Instructions & general Information