Samlexpower EVO-2212E Owner's Manual - Section 1 |
4 | SAMLEX AMErICA INC.
SAMLEX AMErICA INC. | 5
batteries generate hydrogen and Oxygen during charging resulting in evolution of
explosive gas mixture. Care should be taken to ventilate the battery area and follow
the battery manufacturer’s recommendations.
Never smoke or allow a spark or flame near the batteries.
use caution to reduce the risk of dropping a metal tool on the battery. It could spark
or short circuit the battery or other electrical parts and could cause an explosion.
Always use insulated tools.
remove metal items like rings, bracelets and watches when working with batteries.
batteries can produce a short circuit current high enough to weld a ring or the like to
metal and thus cause a severe burn.
If you need to remove a battery, always remove the Ground terminal from the battery
first. Make sure that all the accessories are off so that you do not cause a spark.
tAble 1.1(a) SiZing of griD AnD generAtor inPut wiring AnD breAKerS (for DefAult inPut
current limit ProgrAmmeD At 30A for evo-2212, evo-2224, evo-3012, evo-4024)
model no. and
rated output
Power in in-
verter mode
(column 1)
rated
Ac Pass
through
current
(See note
1)
(column 2)
rated Ac
charging
current
(See note
2)
(column 3)
total rated
Ac input
current
(columns
2 +3)
(See note 3)
(column 4)
Pro-
grammed
Ac input
current
limit
[griD mAX
current/
gen mAX
current]
(See note 4)
(column 5)
nec Ampac-
ity = 125% of
column 5
(See note 5)
(column 6)
conductor
Size based
on nec
Ampacity at
column 6
(See note 6)
(column 7)
external
breaker
Size
based
on nec
Ampacity at
column 6
(See note 7)
(column 8)
EVO-2212
(2200VA, 18A)
18 A
15A
33A
30A
(Default)
37.5A
AWG #8
40A
EVO-2224
(2200VA, 18A)
18A
19A
37A
EVO-3012
(3000VA, 25A)
25A
20A
45A
EVO-4024
(4000VA, 33A)
33A
29A
62A
tAble 1.1(b) SiZing of griD AnD generAtor inPut wiring AnD breAKerS for full rAteD
Ac inPut currentS for evo-2212, evo-2224, evo-3012, evo-4024
model no. and
rated output
Power in in-
verter mode
(column 1)
rated
Ac Pass
through
current
(See note
1)
(column 2)
rated Ac
charging
current
(See note
2)
(column 3)
total rated
Ac input
current
(columns
2 +3)
(See note 3)
(column 4)
Pro-
grammed
Ac input
current
limit
[griD mAX
current/
gen mAX
current]
(See note 4)
(column 5)
nec Ampac-
ity = 125% of
column 5
(See note 5)
(column 6)
conductor
Size based
on nec
Ampacity at
column 6
(See note 6)
(column 7)
external
breaker
Size
based
on nec
Ampacity at
column 6
(See note 7)
(column 8)
EVO-2212
(2200VA, 18A)
18 A
15A
33A
33A
41.25A
AWG #8
45A
EVO-2224
(2200VA, 18A)
18A
19A
37A
37A
46.25A
AWG #8
50A
EVO-3012
(3000VA, 25A)
25A
20A
45A
45A
56.25A
AWG #6
60A
EVO-4024
(4000VA, 33A)
33A
29A
62A
62A
77.5A
AWG #4 or
2X AWG #6
80A
SECTIOn 1 |
Safety Instructions & general Information