Samlexpower EVO-2212E Owner's Manual - Section 6 |
84 | SAMLEX AMErICA INC.
tAble 6.2 ProgrAmmAble AnD DefAult PArAmeterS: grouP chArging curve
Parameter
Programming range
(Programming requires optional re-
mote control model evo-rc)
Default
evo-
2212
evo-
3012
evo-
2224
evo-
4024
evo-
2212
evo-
3012
evo-
2224
evo-
4024
“bulK current”
(bulk Charge Current “Io”)
0-100A
0-130A
0-70A
0-110A
40A
“AbSorP voltAge”
(Absorption Voltage)
13.5V - 16.0V
27.0V - 32.0V
14.4V
28.8V
“eQuAliZe voltAge”
(Equalization Voltage)
14.0V - 16.0V
28.0V - 32.0V
14.4V
28.8V
“floAting voltAge"
(float Voltage)
13.0V - 15.0V
26.0V - 30.0V
13.5V
27.0V
“comPenSAte”
(Temperature Compensation)
-3mV to -5mV /°C/Cell
-4mV /°C/Cell
“low volt AlArm”
(battery Low Voltage Alarm)
9.5V - 12.5V
19.0V - 25.0V
11.0V
22.0V
“bAtt low voltAge”
(battery Low Voltage Shut
Down)
9.1V - 12.0V
18.1V - 24.0V
10.5V
21.0V
“lv Detect time”
(Low Voltage Detect Time)
0-600 sec
10 sec
“lv cut off time”
(Low Voltage Cut Off Time)
0-7200 sec
1200 sec
“reSet voltAge”
(battery Low Voltage reset)
12.0V - 17.0V
24.0V - 35.0V
14.0V
28.0V
“bAtt over volt”
(battery Over Voltage Shut
Down)
14.0V - 17.0V
28.0V - 35.0V
16.0V
32.0V
“chArge moDe”
( 3 or 4 Stage Charging)
Normal (3-Stage) / Equalization (4-Stage)
Normal (3-Stage)
"online moDe" or
"offline moDe"
0 = Off 1 = On
0 = Off
"online oPtionS"
(for on-line and off line
modes)
0 = Option 1
1 = Option 2
0 = Option 1
"floAting eXit"
10.00V to 13.00V
20.00V to 26.00V
12.00V
24.00V
"gS Detect time"
0 - 600 sec
10 sec
"gen on time"
0 - 240 min
60 min
"gen off time"
0 - 240 min
60 min
SECTIOn 6 |
Operation, Protections and Troubleshooting