tAble 6.1 leD AnD buZZer inDicAtionS
Status
green leD
marked “on”
(12, fig 2.1)
red leD
marked
“fault” (13, fig
2.1)
buzzer
Seen during Power-On
Sequence
Indicates completion of
Power-On Sequence after
Power ON/Off button is
pressed for 2 sec
flash 3 times
Off
Off
Seen during Power-Off
Sequence
Indicates completion of
Power-Off Sequence after
Power ON/Off button is
pressed for 5 sec
On
On
Off
Normal charging
flash 1 time per sec Off
Off
Equalization charging
flash 2 times per
sec
Off
Off
Inverting (Discharging)
On
Off
beep per 3 second
(Default Off)
Low battery alarm
On
flash 1 per sec
beep per 1 second
Power saving
flash 1 time per
3 sec
Off
Off
Standby
Off
Off
Off
fault
Off
On
On
6.4 oPtionAl remote control evo-rc (see Appendix A) for
ProgrAmming of moDeS of oPerAtion AnD PArAmeterS
Optional remote Control Model EVO-rC (fig 2.4) will be required for more advanced control
and monitoring. Please see separate Owner’s Manual for EVO-rC at Appendix A. The remote
Control comes with 10M / 33 ft., rJ-45 Data Cable. The remote plugs into rJ-45 Jack on
the front panel of the unit (7, fig 2.1). It has provision for Data Logging using SD Card of up
to 16 Gb (fAT16 / fAT32). It also has its own real Time Clock and Super Capacitor Type of
battery.
Detailed messaging is available through its LCD display and LEDs. This remote will also
be required for programming of various parameters to suit specific requirements. Each
programmable parameter has a Default Value. This unit has been shipped with the various
parameters set at the Default Values. Programmable and Default values are shown in Tables
6.2 to 6.6:
SECTIOn 6 |
Operation, Protections and Troubleshooting