Campbell CCFC Instruction Manual - page 110
CCFC Field Camera
A-1
15.3 Setting Up Datalogger to Work with CCFC: PakBus
Variable Control
The camera is capable of receiving variables, commands, or text
from a datalogger. The specific operational parameters that can be
altered or controlled include:
File Captions
Camera Window Defroster
Camera Shutdown
GPS Coordinates
The use of the Send Variable instruction allows the datalogger to
transfer values or text that can be used in the photo or video
banners. The Send Variable instruction is also used to toggle the
camera window defroster on/off, or safely shut the camera down.
To update the File Caption information with values from a
datalogger the variable is a String and must be limited to 255
characters (including null terminator).
The camera variable names are:
CCFCStillBanner1
CCFCStillBanner2
CCFCVideoBanner1
CCFCVideoBanner2
The variable for controlling the window defroster is numeric and
needs to be declared as a Long in CRBasic. Sending any true or
non-zero value will activate both of these functions. The variable
for controlling camera power is a Boolean, which needs to be
declared in CRBasic. The names of the camera variables are:
CCFCDefroster
CCFCShutdown
Two PakBus variables allow the datalogger to send the GPS
coordinates to the camera where they are embedded in the media
file metadata.
CCFCGPSLatitude
CCFCGPSLongitude