SSD 605C Product Manual - page 124
6-58
Programming Your Application
605C Frequency Inverter
SKIP FREQUENCIES
This function block may be used to prevent
the Inverter operating at frequencies that
cause mechanical resonance in the load.
MMI Menu Map
1 SETUP PARAMETERS
2 FUNCTION BLOCKS
3 SETPOINT FUNCS
4 SKIP FREQUENCIES
SKIP FREQ INPUT
SKIP FREQ BAND 1
SKIP FREQUENCY 1
SKIP FREQ BAND 2
SKIP FREQUENCY 2
SKIP FREQ BAND 3
SKIP FREQUENCY 3
SKIP FREQ BAND 4
SKIP FREQUENCY 4
SKIP FREQ OUTPUT
SKIP FREQ OUTPUT
SKIP FREQ INPUT
SKIP FREQUENCIES
OUTPUT [346] – 0.00 %
OUTPUT HZ [363] – 0.0 Hz
INPUT HZ [362] – 0.0 Hz
0.00 % – [340] INPUT
–
0.0 Hz – [341] BAND 1
–
0.0 Hz – [342] FREQUENCY 1
–
0.0 Hz – [680] BAND 2
–
0.0 Hz – [343] FREQUENCY 2
–
0.0 Hz – [681] BAND 3
–
0.0 Hz – [344] FREQUENCY 3
–
0.0 Hz – [682] BAND 4
–
0.0 Hz – [345] FREQUENCY 4
–
Parameter Descriptions
INPUT
Range: -300.00 to 300.00 %
The value of the block input in %.
BAND 1
Range: 0.0 to 480.0 Hz
The width of each skip band in Hz.
FREQUENCY 1
Range: 0.0 to 480.0 Hz
This parameter contains the centre frequency of each skip band in Hz.
BAND 2
Range: 0.0 to 480.0 Hz
The width of each skip band in Hz.
FREQUENCY 2
Range: 0.0 to 480.0 Hz
This parameter contains the centre frequency of each skip band in Hz.
BAND 3
Range: 0.0 to 480.0 Hz
The width of each skip band in Hz.
FREQUENCY 3
Range: 0.0 to 480.0 Hz
This parameter contains the centre frequency of each skip band in Hz.
BAND 4
Range: 0.0 to 480.0 Hz
The width of each skip band in Hz.
FREQUENCY 4
Range: 0.0 to 480.0 Hz
This parameter contains the centre frequency of each skip band in Hz.
OUTPUT
Range: xxx.xx %
Diagnostic on the output of the function block in %
OUTPUT HZ
Range: xxxx.x Hz
Diagnostic on the output of the function block in Hz
INPUT HZ
Range: xxxx.x Hz
Diagnostic on the input of the function block in Hz