SSD 605C Product Manual - page 224
Application Macros
15-10
605C Frequency Inverter
Macro 4: Process PID
PID error derived from the difference of 2 analog inputs.
Digital input to disable PID.
Additional Operator Menu display parameters.
Terminal
Name
Purpose
Comment
1
ANALOG INPUT 1
Process
Setpoint
0V = 0%, 10V = 100%
2
ANALOG INPUT 2
Process
Setpoint Trim
0V = 0%, 10V = 100%
6
ANALOG OUTPUT 1
Ramp Output
Absolute Speed Demand,
0V = 0%, 10V = 100%
13
DIGITAL INPUT 1
Run
24V = Run
14
DIGITAL INPUT 2
Trip Reset
0V to 24V transition to reset trips.
15
DIGITAL INPUT 3
Direction
0V = Forward, 24V = Reverse
16
DIGITAL INPUT 4
External Trip
0V = Trip
(connect to terminal 18)
17
DIGITAL INPUT 5
PID Enable
0V = PID Disabled,
24V = PID Enabled
21, 22
DIGITAL OUTPUT 1
Health
0V = Tripped, i.e. not healthy
23, 24
DIGITAL OUTPUT 2
Running
0V = Stopped, 24V = Running
The Operator Menu System for Macro 4
The default Operator menu system is shown below.
SETPOINT (REMOTE)
SPEED DEMAND
DRIVE FREQUENCY
MOTOR CURRENT
LOAD
DC LINK VOLTS
CURRENT LIMITING
PROCESS SETPOINT
STARTUP SCREEN
PROCESS FEEDBACK
PID ERROR
PID ENABLE
ENTER PASSWORD