SSD 605C Product Manual - page 232
Application Macros
15-1
8
605C Frequency Inverter
Macro 99: 584S Compatible Application
This macro provides terminal allocation and block diagram
functionality compatible with the 584S product.
Terminal
Name
Purpose
Comment
1
ANALOG INPUT 1
Setpoint
0V = 0%, 10V = 100%
2
ANALOG INPUT 2
Setpoint Trim
0V = 0%, 10V = 100%
3
ANALOG INPUT 3
Current Loop
Setpoint
0mA = 0%, 20mA = 100%
5
ANALOG INPUT 4
Torque Limit
Setpoint
0V = 0%, 10V = 150%
6
ANALOG OUTPUT 1
Ramp Output
Absolute Speed Demand
0V = 0%, 10V = 100%
7
ANALOG OUTPUT 2
Load Output
-10V = -150%,
10V = 150%
13
DIGITAL INPUT 1
Run
24V = Run
14
DIGITAL INPUT 2
Fast Stop
0V - Fast Stop
15
DIGITAL INPUT 3
Direction
0V = Forward, 24V =
Reverse
16
DIGITAL INPUT 4
External Trip
0V = Trip
(connect to terminal 18)
17
DIGITAL INPUT 5
Jog
24V = Jog
18
DIGITAL INPUT 6
Preset 1
Preset Speed Select
19
DIGITAL INPUT 7
Preset 2
Preset Speed Select
20
DIGITAL INPUT 8
Manual/Auto
0V = Manual Setpoint
24V = Auto Setpoint
21, 22
DIGITAL OUTPUT 1
Health
Relay closed = drive healthy
23, 24
DIGITAL OUTPUT 2
Zero Speed
Relay closed = drive at zero
speed
25, 26
DIGITAL OUTPUT 3
At Speed
Relay closed = drive at
speed setpoint
HEALTH
Speed Setpoint
10
k
220V AC 3A maximum
TB1
TB3
TB4
into a resistive load (default)
1 2 3 4 5 6 7 8 9 10
11 12 13 14 15 16 17 18 19 20
DOUT1_A
DOUT1_B
DOUT2_A
DOUT2_B
DOUT3_A
DOUT3_B
21 22 23 24 25 26
AIN1 (SPEED SETPOINT)
AIN2 (SETPOINT TRIM)
AIN3 (CURRENT LOOP)
0V AIN4 (TORQUE LIMIT)
AOUT1 (RAMP OUTPUT)
AOUT2 (LOAD OUTPUT)
+10V REF
0V
-10V REF
+24VC
0V
DIN1 (RUN)
DIN2 (FAST STOP)
DIN3 (DIR)
DIN4 (EXT TRIP)
DIN5 (JOG)
DIN6 (PRESET 1)
DIN7 (PRESET 2)
DIN8 (MANUAL/AUTO)
ZERO SPEED
AT SPEED
General Wiring Diagram for Macro 99
The Operator Menu System for Macro 99
The default Operator menu system is shown below.
SETPOINT (REMOTE)
SPEED DEMAND
DRIVE FREQUENCY
MOTOR CURRENT
LOAD
DC LINK VOLTS
CURRENT LIMITING
PROCESS SETPOINT
STARTUP SCREEN
PROCESS FEEDBACK
PID ERROR
PID ENABLE
ENTER PASSWORD