AUTO RESTART
Auto Restart (or Auto Reset) provides the
facility to automatically reset a choice of
trip events and restart the drive with a
programmed number of attempts, after
which, a manual or remote trip reset is
required if the drive is not successfully
restarted. The number of attempted restarts
are recorded. This count is cleared after a
trip-free period of operation
(5 minutes or 4 x ATTEMPT DELAY 1 ,
whichever is the longer), or after a
successful manual or remote trip reset. This
function is inhibited in Remote Sequencing
Comms mode.
MMI Menu Map
1 SETUP PARAMETERS
2 FUNCTION BLOCKS
3 SEQ & REF
4 AUTO RESTART
AR ENABLE
AR ATTEMPTS
AR INITIAL DLY 1
AR ATTEMPT DLY 1
AR TRIGGERS 1
AR TRIGGERS+ 1
AR INITIAL DLY 2
AR ATTEMPT DLY 2
AR TRIGGERS 2
AR TRIGGERS+ 2
AR PENDING
AR RESTARTING
AR ATTEMPTS
LEFT
AR TIME LEFT
AUTO RESTART
PENDING [608] – FALSE
RESTARTING [616] – FALSE
ATTEMPTS LEFT [614] – 5
TIME LEFT [615] – 10.0 s
FALSE – [611] ENABLE
–
5 – [612] ATTEMPTS
–
10.0 s – [610] INITIAL DELAY 1
–
10.0 s – [613] ATTEMPT DELAY 1
–
0000 – [609] TRIGGERS 1
–
0000
[744] TRIGGERS+ 1
–
0.1 s – [678] INITIAL DELAY 2
–
0.1 s – [679] ATTEMPT DELAY 2
–
0000 – [677] TRIGGERS 2
–
0000
[745] TRIGGERS+ 2
–
Parameter Descriptions
ENABLE
Range: FALSE / TRUE
Enables operation of the auto restart feature.
ATTEMPTS
Range: 1 to 10
Determines the number of restarts that will be permitted before requiring an external fault
reset.
INITIAL DELAY 1
Range: 0.0 to 600.0 s
Determines the delay for the first restart attempt when the trip is included in TRIGGERS 1 .
The delay is measured from all error conditions clearing.
ATTEMPT DELAY 1
Range: 0.0 to 600.0 s
Determines the delay between restart attempts for a trip included in TRIGGERS 1 . The delay
is measured from all error conditions clearing.
TRIGGERS 1 and TRIGGERS+ 1
Range: 0000 to FFFF
Allows Auto Restart to be enabled for a selection of trip conditions.
Refer to “Hexadecimal Representation of Trips” at the beginning of this chapter for an
explanation of the four-digit codes.
INITIAL DELAY 2
Range: 0.0 to 600.0 s
Determines the delay for the first restart attempt when the trip is included in TRIGGERS 2
The delay is measured from all error conditions clearing.
ATTEMPT DELAY 2
Range: 0.0 to 600.0 s
Determines the delay between restart attempts for a trip included in TRIGGERS 2 . The delay
is measured from all error conditions clearing.
TRIGGERS 2 and TRIGGERS+ 2
Range:0000 to FFFF
Allows Auto Restart to be enabled for a selection of trip conditions.
If a trip is included in both TRIGGERS 1 and TRIGGERS 2, then the times associated with
TRIGGERS 1 will take priority.
Refer to “Hexadecimal Representation of Trips” at the beginning of this chapter for an