SSD 605C Product Manual - Control Terminals
11-6
Technical Specifications
605C Frequency Inverter
Control Terminals
Terminal
No.
Block
No.
Name
Range
Description
TB1 : ANALOG I/O TERMINAL BLOCK
This is a 10-way connector carrying all customer analog I/O.
1
TB1-1
AIN1 (SPEED)
0-10V, ±10V,
0-20mA, 4-20mA
Configurable analog input
Default function = Speed Setpoint
2
TB1-2
AIN2 (TRIM)
0-10V, ±10V,
0-20mA, 4-20mA
Configurable analog input
Default function = Speed Trim
3
TB1-3
AIN3
0-20mA, 4-20mA
Configurable analog input
4
TB1-4
0V
0V reference for analog i/o
5
TB1-5
AIN4
0-10V
Configurable analog input
6
TB1-6
AOUT1 (RAMP)
0-10V,
0-20mA, 4-20mA
Configurable analog output
Default function = Ramp Output
7
TB1-7
AOUT2
±10V
Configurable analog output
Default function = Ramp Output
8
TB1-8
+10V REF
10V
10V reference for analog i/o
Load 5mA maximum
9
TB1-9
0V
0V
0V reference for digital i/o
10
TB1-10 -10V REF
-10V
-10V reference for analog i/o
Load 5mA maximum
TB3 : DIGITAL INPUT TERMINAL BLOCK
This is a 10-way connector carrying all digital inputs.
11
TB3-1
+24VC
Customer +24V (max load 150mA)
12
TB3-2
0V
All inputs below 24V=high , 0V=low
13
TB3-3
DIN1 (RUN)
0-24V
Configurable digital input
Default function = RUN
0V = Stop, 24V = Run
14
TB3-4
DIN2 (TRIP RESET) 0-24V
Default function = Trip Reset
15
TB3-5
DIN3 (DIR)
0-24V
Configurable digital input
Default function = DIRECTION
24V = Reverse, 0V = Forward
16
TB3-6
DIN4 (EXT TRIP)
0-24V
Configurable digital input
Default function = EXTERNAL TRIP (active low)
24V = No Trip, 0V = Trip
17
TB3-7
DIN 5 (JOG)
0-24V
Configurable digital input
Default function = JOG
24V = Jog, 0V = Stop
18
TB3-8
DIN6
0-24V
Default function: NON-USER DEFINED
19
TB3-9
DIN7
0-24V
Default function: NON-USER DEFINED
20
TB3-10 DIN8
0-24V
Default function: NON-USER DEFINED
TB4 : RELAY OUTPUT TERMINAL BLOCK
These relay ouputs are volt-free, normally-open contacts rated to 250V,
3A with resistive load. Connection is by a 6-way spring clamp connector.
21
22
TB4
DOUT1_A
DOUT1_B
normally-open
relay contacts
Default Function DOUT1 closed = Healthy
23
24
TB4
DOUT2_A
DOUT2_B
normally-open
relay contacts
Default Function DOUT2 closed = Running
25
26
TB4
DOUT3_A
DOUT3_B
normally-open
relay contacts
Default Function NON-USER DEFINED